Mitsubishi Electronics Q64TCTTN ユーザーズマニュアル

ページ / 430
390
Appendix 4.3
Operations when performing an online module 
change
The following table shows the operations of the Q64TCN when an online module change is performed.
: Executed ×: Not executed
*1
An access to Intelligent function module device (U\G) is included.
*2
The intelligent function module operates according to the previous setting when the user does not perform any 
operation.
(4) Check the operation.
(5) Restart the control.
Check the operation before the control starts.
(2) Remove the module.
Start the online module change 
using GX Developer.
Click the             button on 
GX Developer to enable t
he module to be removed.
Remove the selected module.
(3) Mount a new module.
Mount a new module.
After mounting the module, 
click             on GX Developer.
Click the             button on 
GX Developer to turn off 
the online mode.
On "Device test" on GX Developer 
or on "Monitor/Test    " on GX 
Configurator, test the operation of 
the module.
Operation check is completed.
Restart the online module change 
using GX Developer. Click the 
             button to restart the control.
The module is normally 
operating.
The operation of the module 
has stopped. 
   The RUN LED turns off.
The X/Y refresh restarts and 
the module starts up.
   The RUN LED turns on.
   Default operation 
  (Module READY flag (Xn0) 
  stays off.)
When there are initial 
setting parameters, the 
module starts to operate 
based on the initial setting 
parameters at this point.
The module operates based 
on the test operation
*2
.
Module ready flag (Xn0) 
turns on.
The module operates based on 
the initial setting sequence 
program started
*2
 when Module 
READY flag (Xn0) is started.
(1) Stop the operation.
Turn off all the Y signals turned on by 
the sequence program.
User operation
Operation of 
the Q64TCN
Operation of the CPU module
GX Configurator-TC
X/Y 
refresh
Device 
test
Initial 
setting 
parameters
Monitor/
Test    
FROM/TO 
instructions
*1