Mitsubishi Electronics Q64TCTTN ユーザーズマニュアル
392
Appendix 4.5
When GX Configurator-TC was used for the initial
setting
setting
(1) Stopping operation
When PID continuation flag (Un\G169) is set to Continue (1), control does not stop even if Setting/operation mode instruction
(Yn1) is turned off. Change PID continuation flag (Un\G169) to Stop (0) and turn off Setting/operation mode instruction
(Yn1).
Whether the control has been stopped can be checked by Setting/operation mode status (Xn1) being off.
(Yn1) is turned off. Change PID continuation flag (Un\G169) to Stop (0) and turn off Setting/operation mode instruction
(Yn1).
Whether the control has been stopped can be checked by Setting/operation mode status (Xn1) being off.
1.
Open the "Device test" window.
[Online]
[Debug]
[Device
test...]
2.
Turn off the following output signals to stop the
operation of the module.
• Setting/operation mode instruction (Yn1)
• E
2
PROM backup instruction (Yn8)
• Default setting registration instruction (Yn9)
• Setting change instruction (YnB)
• Setting change instruction (YnB)