Mitsubishi Electronics 13JW55 ユーザーズマニュアル

ページ / 350
 
 
7 - 18
 
 
 
7.6.2  D/A conversion characteristics 
(1)  D/A conversion characteristics on voltage outputs 
(For analog output range from -10 to 10V in a standard resolution mode) 
 
A
n
a
log
 ou
tp
u
t v
o
lt
a
g
e
5.0025V
Digital input
0
0
Digital input value
10V
4000
-10V
- 4000
5.0000V
2000 20012002 2003 2004
2.5mV
Analog
 ou
tp
u
volt
ag
e
 
Figure 7.14    D/A conversion characteristics (current output) 
 
D/A converter modules convert digital quantities that are input from a QCPU 
into analog values, and then output them. For example, the modules convert a 
digital quantity of -4000 to a analog quantity of -10V and 4000 to 10V before 
output. This means that the modules convert the digital input value of 1 to an 
analog quantity of 2.5mV, and abandon digital input values in decimal places. 
 
(2)  D/A conversion characteristics on current outputs 
(For analog output range from 0 to 20mA in a standard resolution mode) 
 
A
n
a
lo
g
 o
u
tp
u
c
u
rr
e
n
t
10.005mA
Input
0
0
A
n
a
lo
g
 o
u
tp
u
c
u
rr
e
n
t
Digital input value
20mA
4000
-20mA
-4000
10.000mA
200020012002 2003
5   A
 
Figure 7.15    D/A conversion characteristics (current output) 
 
For current outputs, the modules convert a digital value 0 to 0mA and 4000 to 
20mA. This means that the modules convert the digital input value of 1 to an 
analog quantity of 5
μA, and abandon digital input values in decimal places. 
 
REMARK 
 
A voltage or current value that is equivalent to a digital value of 1 through D/A 
conversion (maximum resolution) differs depending on the setting of the 
resolution mode (1/4000, 1/12000, 1/16000) or the output range.