Emerson Network Router ユーザーズマニュアル

ページ / 110
24
ProLink
®
 II Software for Micro Motion
®
 Transmitters
Installation and Setup
Method 9: Modbus/RS-485 temporary connection to MVD Direct Connect
Using a Black Box signal converter, the PC can be connected directly to the RS-485 terminals on the 
core processor or the MVD Direct Connect I.S. barrier.
1. At the PC, attach the Black Box signal converter to the PC’s serial or USB port, using a 25-pin 
to 9-pin adapter if necessary.
2. If connecting to the core processor, remove the lid.
3. Connect the signal converter leads to the RS-485 terminals. See Table 2-12, and:
For connecting to the standard core processor, see Figure 2-10.
For connecting to the enhanced core processor, see Figure 2-11.
For connecting to the I.S. barrier, see Figure 2-12.
Note: The Modbus protocol allows only one Modbus master to be active on the network at any given 
time. If you are connecting through a network, ensure that no other Modbus master devices are 
currently active.
Note: Before using ProLink II to communicate with the core processor, disconnect any wiring to a 
remote PLC. Be careful not to disconnect the power supply wiring. After using ProLink II to 
communicate with the core processor, reconnect the wiring to the remote PLC.
Figure 2-10
Modbus/RS-485 connection to RS-485 terminals on standard core processor 
Table 2-12
Lead-to-terminal assignments – Method 9
Device
Terminals
RS-485/A
RS-485/B
I.S. barrier
(1)
(1) Connection is intrinsically safe.
13
14
Core processor
(2)
(2) Connection is not intrinsically safe.
3
4
Core processor
RS-485 to RS-232 
signal converter
25 to 9 pin serial port 
adapter (if necessary)
RS-485/B
RS-485/A