Site Requirements and Prerequisites
2-1
Chapter 2
Installation
Installation
2.1 Introduction
IPmux-16 is delivered completely assembled for bench-top installation. The only
mechanical installation procedure that may be necessary is optional installation in
mechanical installation procedure that may be necessary is optional installation in
a 19-inch rack.
After installing the unit, configure the IPmux-16 using an ASCII terminal connected
to the IPmux-16 control port. The IPmux-16 configuration procedures are
After installing the unit, configure the IPmux-16 using an ASCII terminal connected
to the IPmux-16 control port. The IPmux-16 configuration procedures are
described in Chapter 3 of this manual.
If problems are encountered, refer to Chapter 4 for test and diagnostics
If problems are encountered, refer to Chapter 4 for test and diagnostics
instructions.
No internal settings, adjustment, maintenance and repairs may be performed
by either the operator or the user; such activities may be performed only by
skilled service personnel who are aware of the hazards involved.
skilled service personnel who are aware of the hazards involved.
Always observe standard safety precautions during installation, operation, and
maintenance of this product.
2.2 Site Requirements and Prerequisites
AC-powered IPmux-16 units should be installed within 1.5m (5 feet) of an
easily-accessible grounded AC outlet capable of furnishing the required supply
easily-accessible grounded AC outlet capable of furnishing the required supply
voltage, in the range of 100 to 240 VAC, 16A maximum.
DC-powered IPmux-16 units require a –48 VDC power source (positive pole
DC-powered IPmux-16 units require a –48 VDC power source (positive pole
grounded).
The DC power source must be isolated from the mains supply by double or
reinforced insulation.
reinforced insulation.
Allow at least 90 cm (36 in) of frontal clearance for operator access. Allow at least
10 cm (4 in) clearance at the rear of the unit for cable connections. Make sure that
the ventilation holes are not blocked.