2.1 Introduction 
IPmux-16 is delivered completely assembled for bench-top installation. The only 
mechanical installation procedure that may be necessary is optional installation in 
a 19-inch rack.  
After installing the unit, configure the IPmux-16 using an ASCII terminal connected 
to the IPmux-16 control port. The IPmux-16 configuration procedures are 
described in Chapter 3 of this manual.  
If problems are encountered, refer to Chapter 4 for test and diagnostics 
instructions. 
 
 
No internal settings, adjustment, maintenance and repairs may be performed 
by either the operator or the user; such activities may be performed only by 
skilled service personnel who are aware of the hazards involved. 
Always observe standard safety precautions during installation, operation, and 
maintenance of this product. 
 
 
2.2  Site Requirements and Prerequisites 
AC-powered IPmux-16 units should be installed within 1.5m (5 feet) of an 
easily-accessible grounded AC outlet capable of furnishing the required supply 
voltage, in the range of 100 to 240 VAC, 16A maximum. 
DC-powered IPmux-16 units require a –48 VDC power source (positive pole 
grounded). 
 
 
The DC power source must be isolated from the mains supply by double or 
reinforced insulation.  
 
Allow at least 90 cm (36 in) of frontal clearance for operator access. Allow at least 
10 cm (4 in) clearance at the rear of the unit for cable connections. Make sure that 
the ventilation holes are not blocked. 