Patton electronic 07MOS10xx-GS ユーザーズマニュアル

ページ / 67
OnSite System Installation
34
OnSite Series Getting Started Guide 
3 • Installation Overview
Note
The DC-to-DC converter has dual power inputs (A and B power). 
The system continues to operate normally if either the A or B power 
input fails.
The system uses natural convection for heat dissipation (that is, it does not use fans). The absence of fans 
increases system reliability and eliminates periodic maintenance visits for fan filter replacement.
 pro-
vides the maximum power consumption figures for the OS-10 system under normal operating conditions.
This section explains how to connect the AC or DC power to the OS-10 system chassis. 
The installation must comply with all required electrical codes applicable at the installation site.
Connecting AC Power to the OS-10 System
If your OS-10 system uses AC power, connect it to a 15 A at 120 VAC (or 10 A at 240 VAC) circuit with over-
current protection.
Note
The input voltage tolerance limits for AC power are 100 to 245 VAC.  
Table 8. Power Consumption
System Configuration
Maximum Power (W)
Base system
40
Base system with a single expansion module
50
Base system with dual expansion modules
60
Read the installation instructions before connecting the system to the power 
source.
Do not work on the system or connect or disconnect cables during periods of 
lightning activity.
•AC-connected units must have a permanent ground connection in addition to 
the power cable ground wire. NEBS-compliant grounding satisfies this 
requirement.
•This product relies on the installation of the building for short-circuit (over-
current) protection. Ensure that the protective device is rated not greater 
than: 15A at 120 VAC (or 10 A at 240 VAC).
•The AC power supply for the OS-10 system has Double Pole/Neutral Fusing.
WARNING
WARNING
WARNING