Mitsubishi Electronics QD75MH2 ユーザーズマニュアル

ページ / 838
 
 
 
12 - 61 
MELSEC-Q
 
12   CONTROL SUB FUNCTIONS 
 
12.7 Other functions 
Other functions include the "step function", "skip function", "M code output function", 
"teaching function", "target position change function", "command in-position function", 
"acceleration/deceleration processing function", "pre-reading start function", " 
deceleration start flag function" and "stop command processing for deceleration stop 
function" and "follow up processing function". Each function is executed by parameter 
setting or PLC program creation and writing.  
 
12.7.1 Step function 
The "step function" is used to confirm each operation of the positioning control one by 
one.  
It is used in debugging work for major positioning control, etc. 
A positioning operation in which a "step function" is used is called a "step operation".  
In step operations, the timing for stopping the control can be set. (This is called the 
"step mode".) Control stopped by a step operation can be continued by setting "step 
continue" (to continue the control)" or restarted by setting "restart" in the "step start 
information".  
 
The details shown below explain about the "step function".  
  [1] Relation between the step function and various controls 
  [2] Step mode 
  [3] Step start information 
  [4] Using the step operation  
  [5] Control details 
  [6] Precautions during control 
  [7] Step function settings 
 
[1]   Relation between the step function and various controls 
The following table shows the relation between the "step function" and various 
controls. 
 
Control type 
Step function 
Step applicability 
Machine OPR control 
 
OPR control 
Fast OPR control 
 
Step operation not possible 
1-axis linear control 
 
2 to 4-axes linear interpolation control 
 
1-axis fixed-feed control 
 
2 to 4- axes fixed-feed control 
(interpolation) 
 
Position 
control 
2-axis circular interpolation control 
 
Step operation possible 
1 to 4- axes Speed control 
 
Step operation not possible 
Speed-position switching control 
Position-speed switching control 
 
Current value changing 
 
Step operation possible 
Major 
positioning 
control 
Other 
control  JUMP instruction, NOP instruction, 
LOOP to LEND 
 
Step operation not possible 
JOG operation, Inching operation 
 
Manual 
control 
Manual pulse generator operation 
 
Step operation not possible 
 
                 : Set when required.   : Setting not possible