Mitsubishi Electronics QD75MH2 ユーザーズマニュアル

ページ / 838
 
 
 
12 - 63 
MELSEC-Q
 
12   CONTROL SUB FUNCTIONS 
 
[4]   Using the step operation  
The following shows the procedure for checking positioning data using the step 
operation.  
(1)   Turn ON the step valid flag before starting the positioning data.  
(Write "1" (carry out step operation) in "
Cd.35
 Step valid flag".) 
 
(2)   Set the step mode before starting the positioning data. 
(Set in "
Cd.34
 Step mode".) 
 
(3)   Turn ON the positioning start signal, and check that the 
positioning control starts normally.  
 
(4)   The control will stop for the following reasons. 
 a)  One step of positioning stopped normally.   Go to step (6). 
 b)  Control stopped by a stop signal.    Take appropriate measures, go to 
step (5). 
 c)  An error occurred and the control stopped.    Take appropriate 
measures, go to step (3). 
 
(5)   Write "1" (restart) to "
Cd.6
Restart command", and check that 
the positioning data where the control stopped operates 
normally.   Go to step (4). 
 
(6)   Write "1" (step continue) to "
Cd.36
 Step start information", and 
check that the next positioning data operates normally. 
 a)  One step of positioning stopped normally.   Go to step (6). 
 b)  Control stopped by a stop signal.   Take appropriate measures, go to 
step (5). 
 c)  An error occurred and the control stopped.   Take appropriate 
measures, go to step (3). 
 d)  All positioning data operated normally.   Go to step (7). 
 
(7)   Turn OFF the step valid flag, and quit the "step function".  
(Write "0" (do not carry out step operation) in "
Cd.35
 Step valid flag".)