12 - 65 
MELSEC-Q
 
12   CONTROL SUB FUNCTIONS 
 
[6]   Precautions during control 
(1)  When step operation is carried out using interpolation control positioning 
data, the step function settings are carried out for the reference axis.  
 
(2)  When the step valid flag is ON, the step operation will start from the 
beginning if the positioning start signal is turned ON while "
Md.26
 Axis 
operation status" is "step standing by". (The step operation will be carried 
out from the positioning data set in "
Cd.3
 Positioning start No.".) 
 
[7]   Step function settings 
To use the "step function", write the data shown in the following table to the 
QD75 using the PLC program. Refer to section [4] "Using the step operation" for 
the timing of the settings. 
The set details are validated when written to the QD75MH. 
 
Buffer memory address 
Setting item 
Setting 
value 
Setting details 
Axis 
Axis 
Axis 
Axis 
 Cd.34    Step mode 
 
Set "0: Deceleration unit step" or "1: Data No. 
unit step". 
1544 1644 1744 1844 
 Cd.35    Step valid flag 
Set "1: Carry out step operation". 
1545  1645  1745  1845 
 Cd.36   
Step start 
information 
 
Set "1: Step continue", depending on the stop 
status. 
1546 1646 1746 1846 
 
                   Refer to Section 5.7 "List of control data" for details on the setting details.