12.3 Error Code List  
12.3.8  Error code list (8000 to 9000)
12
 - 52
9
EM
C AN
D
 L
O
V
O
LT
AG
DI
RE
C
T
IV
E
S
10
LO
A
D
ING A
ND 
INS
TA
LLA
T
ION
11
M
A
INT
E
NANCE
 AND 
IN
SP
ECT
IO
N
12
T
R
O
U
BL
ES
HO
O
T
IN
G
 A
PPE
NDICES
 INDEX
 
 
Error 
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding 
CPU
8000
Error is detected by the inside register 
diagnostics built in the CPU module.
This suggests a CPU module hardware 
fault. (Please consult your local 
Mitsubishi representative.)
QS
8010
Error is detected inside the bus of the 
CPU module.
This suggests a CPU module hardware 
fault. (Please consult your local 
Mitsubishi representative.)
QS
8020
Mismatch has occurred in the execution 
status of CPU A and CPU B.
• Take measure against noise.
• Reset it and run it again. 
If the same error is displayed again, this 
suggests a CPU module hardware fault. 
(Please consult your local Mitsubishi 
representative.)
QS
8021
Mismatch of program execution times is 
detected between CPU A and CPU B.
8031
Error of a file stored in the program 
memory or the standard ROM is 
detected.
The file indicated by the individual 
information SD17~SD22 is written into 
the individual information SD16, and 
turn the CPU power is turned OFF ON 
or reset reset canceling.If the same 
error is displayed again, this suggests a 
CPU module hardware fault. (Please 
consult your local Mitsubishi 
representative.)
QS
8032
8050
The verification of safety outputs 
between the CPU A and CPU B in a 
CPU module resulted in a mismatch.
• Check if the program for outputing 
safety outputs is correct.
• Take measure against noise.
• Reset it and run it again.
If the same error is displayed again, this 
suggests a CPU module hardware fault. 
(Please consult your local Mitsubishi 
representative.)
QS
*3
This applies when the serial number (first five digits) of the CPU module is "13042" or later.