Mitsubishi Electronics QSPCU ユーザーズマニュアル

ページ / 224
12
 - 53
12.3 Error Code List  
12.3.8  Error code list (8000 to 9000)
12
TROUBLESHOOTING
8060
INCORRECT 
FIRMWARE
Error 
information
Off
Flash
Stop
At power ON/ 
At reset/When 
an END 
instruction 
executed.
8070
INTERNAL 
CPU 
COMMUNI-
CATION 
ERROR
Error 
information
Off
Flash
Stop
At power ON/ 
At reset
8071
8072
8073
When an END 
instruction 
executed.
8074
8080
POWER 
SUPPLY 
ERROR
Error 
information
Off
Off/On
Stop
Always
8090
VOLTAGE 
DIAGNOSIS 
ERROR
Error 
information
Off
Flash
Stop
When an END 
instruction 
executed.
8100
TEST MODE 
TIME 
EXCEEDED
On
On
Continues
When an END 
instruction 
executed.
8120
WDT CLOCK 
CHECK 
ERROR
Off
Flash
Stop
Always
8300
CC-LINK 
REMOTE 
DETECTION 
ERROR
CC-Link Safety 
information
CC-Link Safety 
information
Off/On
*1
Flash/
On
*1
Stop/
Continues
*1
Always
Error 
Code
(SD0)
Error 
Message
Common 
Information
(SD5 to 15)
Individual 
Information
(SD16 to 26)
LED Status
CPU 
Operation 
Status
Diagnostic 
Timing
RUN
ERROR
*1
The operating status of a CPU module in case of an error can be set in the "Operation settings during remote station error" of "Parameter". The default is set 
to "Stop" (The LED indication changes according to the status).
*2
At occurrence of "F****", the “USER” LED turns on.