Emerson BACNET IP ユーザーズマニュアル
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
88
Table 30
Liebert Mini-Mate2
™
8 Ton - Input and Holding - L8T
Controller
L8T
Liebert Products
Liebert Mini-Mate2 8 Ton
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes
/
Units
Status Points (View)
Temperature
Temperature
—
40001
1
—
—
Humidity
—
40002
1
—
—
Cooling
—
40003
1
—
1=On / 0=Off
Heating
—
40004
1
—
1=On / 0=Off
Humidification
—
40005
1
—
1=On / 0=Off
De-humidification
—
40006
1
—
1=On / 0=Off
Econ-O-Cycle
—
40007
1
—
1=On / 0=Off
Stages
—
40008
1
—
—
% Capacity
—
40009
1
—
—
Analog input 1
—
40023
1
—
A/D raw value w/ slope =1
and offset = 0
Analog input 2
—
40024
1
—
A/D raw value w/ slope =1
and offset = 0
Analog input 3
—
40025
1
—
A/D raw value w/ slope =1
and offset = 0
Analog input 4
—
40026
1
—
A/D raw value w/ slope =1
and offset = 0
Alarm Points
Communications
Communications
—
40289
1
—
Bit 0
Local Off
—
40289
1
—
Bit 1
Remote Off
—
40289
1
—
Bit 2
High Head Pressure 1
—
40289
1
—
Bit 3
High Head Pressure 2
—
40289
1
—
Bit 4
Loss of Airflow
—
40289
1
—
Bit 5
Standby Glycol Unit On
—
40289
1
—
Bit 6
Not Used
—
40289
1
—
Bit 7
Change Filters
—
40289
1
—
Bit 8
High Temperature
—
40289
1
—
Bit 9
Low Temperature
—
40289
1
—
Bit 10
High Humidity
—
40290
1
—
Bit 0
Low Humidity
—
40290
1
—
Bit 1
Humidifier Problem
—
40290
1
—
Bit 2
Smoke Detected
—
40290
1
—
Bit 8
Loss of Water
—
40290
1
—
Bit 9
Standby Unit On
—
40290
1
—
Bit 10
Not Used
—
40291
1
—
Bit 0
Short Cycle
—
40291
1
—
Bit 1
Loss of Power
—
40291
1
—
Bit 2
Local Alarm 1
—
40291
1
—
Bit 6
Local Alarm 2
—
40291
1
—
Bit 7