Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
88
Table 30
Liebert Mini-Mate2
 8 Ton - Input and Holding - L8T
Controller
L8T
Liebert Products
Liebert Mini-Mate2 8 Ton
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes 
Units
Status Points (View)
Temperature
40001
1
Humidity
40002
1
Cooling
40003
1
1=On / 0=Off
Heating
40004
1
1=On / 0=Off
Humidification
40005
1
1=On / 0=Off
De-humidification
40006
1
1=On / 0=Off
Econ-O-Cycle
40007
1
1=On / 0=Off
Stages
40008
1
% Capacity
40009
1
Analog input 1
40023
1
A/D raw value w/ slope =1
and offset = 0
Analog input 2
40024
1
A/D raw value w/ slope =1
and offset = 0
Analog input 3
40025
1
A/D raw value w/ slope =1
and offset = 0
Analog input 4
40026
1
A/D raw value w/ slope =1
and offset = 0
Alarm Points
Communications
40289
1
Bit 0
Local Off
40289
1
Bit 1
Remote Off
40289
1
Bit 2
High Head Pressure 1
40289
1
Bit 3
High Head Pressure 2
40289
1
Bit 4
Loss of Airflow
40289
1
Bit 5
Standby Glycol Unit On
40289
1
Bit 6
Not Used
40289
1
Bit 7
Change Filters
40289
1
Bit 8
High Temperature
40289
1
Bit 9
Low Temperature
40289
1
Bit 10
High Humidity
40290
1
Bit 0
Low Humidity
40290
1
Bit 1
Humidifier Problem
40290
1
Bit 2
Smoke Detected
40290
1
Bit 8
Loss of Water
40290
1
Bit 9
Standby Unit On
40290
1
Bit 10
Not Used
40291
1
Bit 0
Short Cycle
40291
1
Bit 1
Loss of Power
40291
1
Bit 2
Local Alarm 1
40291
1
Bit 6
Local Alarm 2
40291
1
Bit 7