Operating Instructions
84
9.8.3 Shutdown Procedure—Complete UPS and Load Shutdown
This procedure must be followed to completely power down the UPS and the load. All power switches, 
isolators and circuit breakers will be opened and power will be removed from the load.
In multi-module systems, perform each step of the procedure in every UPS module before proceeding 
to the next step.
1. Press the EPO (Emergency Power Off) button at the UPS front panel only. This will disable 
Rectifier, Inverter, Static Switch and Battery operation. The load will be de-energized.
2. Open the UPS door to gain access to the main circuit breakers.
3. Open the Rectifier input circuit breaker CB1.
4. Open external battery circuit breaker. This breaker is inside the battery cabinet or is otherwise 
adjacent to the battery racks.
5. Open Output circuit breaker CB5.
6. Open bypass input circuit breaker CB2.
7. Ensure maintenance bypass circuit breaker CB3 is open.
8. All mimic panel LED indications and messages will extinguish as the mains-driven, internal 
power supplies decay.
9. To completely isolate the UPS from the AC supplies, the main external power input isolator (both 
isolators, where dual supplies are provided for rectifier and bypass) and external output isolator 
must be opened and tagged with warning labels accordingly.
9.9
Commissioning a Parallel System
Check the input and output wiring of each UPS module. Ensure that the phase rotation sequence of 
the main inputs and the bypass inputs and outputs of each UPS module are the same. Ensure that 
the parallel cables are connected firmly.
It is assumed that the installation is complete, the system has been commissioned by authorized per-
sonnel and the external power isolators are closed. Disconnect the load before startup.
9.10 Parallel System Startup
1. Start each UPS normally as described in 9.2 - UPS Startup
2. Turn on the inverter of each UPS module one at a time.
3. Apply the load after the last UPS module transfers to inverter. The total load can be determined 
through the LCD of either UPS.
4. Verify the load rate of each UPS module. If the load rates are roughly the same, then the parallel 
system may be assumed to be operating normally.
!
CAUTION
This procedure will shut off power to the load.
NOTE
Before beginning this procedure, shut down the connected load to prevent the possibility of 
damage.
!
CAUTION
Except in an emergency situation, do not press any remote EPO button
!
CAUTION
The operations described in this section must be performed by authorized electricians or 
qualified technical personnel. If you have any difficulty, call 1-800-LIEBERT for assistance.
NOTE
If one module cannot transfer to inverter mode long after its inverter is on, its output 
connection may not be good or its output phase rotation may not be coincident with other 
modules. At this time, the LCD for the UPS module will display “inverter asynchronous” and 
the inverter indicator will flash continuously. If either UPS module makes abnormal noise 
after it transfers to inverter, its parallel cables may be incorrectly connected.