Several items of optional equipment are available for connection to the Liebert NX UPS.
10.1 Communication and Other User Terminals
The UPS can be integrated into advanced networking environments via UPS monitoring software 
such as Microsoft UPS Monitor
, Liebert MultiLink
, Liebert Nform
, Liebert SiteNet
, Modbus / 
Jbus, Liebert SiteScan
, Liebert SiteScan 2
, SNMP, etc. They allow UPS status monitoring and 
automatic and safe shutdown of the server and PCs.
Figure 61 Monitoring board (U2) auxiliary terminal block detail
10.1.1 Analog Input Interface
At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is 
2 percent. “ENV-T” is used for environment temperature detecting.
• X6 pin 1: Not used
• X6 pin 2: +12V
• X6 pin 3: ENV-T – environment temperature detection
• X6 pin 4: GND
10.1.2 Power Output
The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to 
12V. The maximum current is 500mA.
10.1.3 Liebert IntelliSlot Communication
The Liebert NX has three Liebert IntelliSlot ports to allow field-installation of optional communica-
tion cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary ESP2 protocol to cards that 
translate the information into such protocols as SNMP, IGMnet, Modbus or Jbus. Other cards provide 
dry contact signals for external signaling of operating status.
The Liebert IntelliSlot communication ports may be installed or removed while the Liebert NX is 
operating.
NOTE: The black square ()
on each slot indicates Pin 1.
J3
J1
J13 J21 J25
J28
J4
J26 J30 J10
J22
J23
J12
J9
J15
J17
J24
X4
X4
J16
X1
X2
X3
Liebert IntelliSlot 2
Liebert IntelliSlot 1
Liebert IntelliSlot 3
J8
J2
LCD
BFP INV ACF
EPO
Dry in
MBC
BCB
X5
X6
X7
PWR
MODEM
SNMP CARD