Installing the HP UPS Management Module  22 
1. 
On the host computer, click Start, and select 
Programs>Accessories>Communications>HyperTerminal. 
The Connection Description window appears. 
2. 
Enter a description, select an icon for the connection, and then click OK. The Connect To window 
appears. 
3. 
Select the serial connector on the host computer to which the DB-9 to RJ-45 adapter is attached, and 
then click OK. The COM Properties window appears. 
4. 
Select the following parameter values, and then click OK. 
Bits per second—115200 
Data bits—8 
Parity—None 
Stop bits—1 
Flow control—None 
 
Configuring the management module for remote 
access 
1. 
Be sure that you have connected the network cable ("
the management module. 
2. 
Be sure that you have connected the configuration cable ("
page 
) to the management module and the host computer with an open terminal emulation 
session. 
3. 
Press the Reset button on the management module front panel. 
 
On the terminal emulation session screen running on the host computer, the POST executes, and the 
following prompt appears: 
Press any key in 5 seconds to enter Service menu.
 
4. 
Press a key to enter the HP UPS Management Module Service Menu.