American Power Conversion 200/208 V ユーザーズマニュアル

ページ / 52
28
Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide 
990-2359A
Battery Replacement 
General safety prior to module replacement
Battery Module
One Battery Module consists of 4 Battery Units (max. 2 Battery Modules shipped in the Enclosures).
WARNING!
• Only trained personnel familiar with the operation of the equipment, and the 
electrical and mechanical hazards involved, may install and remove system 
components.
• The UPS and Battery Enclosure contain an internal energy source. Hazardous 
voltage may be present even when disconnected from the power source. Follow 
Total Power Off Procedure to completely de-energize the system.
• Never replace batteries when the UPS is running in battery mode!
• Risk of Energy Hazard, 96 V, 7.2 Ampere-hour battery. Before replacing 
batteries, remove all conductive jewelry such as chains, watches, and rings. 
High energy through conductive materials could cause severe burns. 
• Batteries do not contain serviceable parts. Do not open.
• Do not open or mutilate batteries. Released material is harmful to the skin and 
eyes. It may be toxic. Do not dispose of batteries in a fire, as they may explode.
• To ensure continuous battery back-up, only replace one Battery Module at a 
time.
• For configurations that include customer-supplied external batteries, refer to 
manufacturer’s battery installation and maintenance instructions.
Two people to lift a component weighing between 18 – 32 kg. 
4 x 23kg