AEG PROTECT B. 1500 ユーザーズマニュアル

ページ / 54
48
PROTECT B. 750 and B.1000
1.
Unscrew  the  two  screws  on  the  side  and  remove  the 
front  panel  carefully  on  both  ends.  Make  sure  that  the 
panel does not tilt too much. 
2.
Disconnect the battery cable from the UPS and remove 
the  battery  retaining  battery  bracket  to  the  right  so  that 
the battery can be pulled out to the front. 
3.
Withdraw the new batteries from the transport container 
an  put  into  the  right  position.  Fix  both  blocks  together 
and  connect  the  electric  connections  of  the  extracted 
battery system. 
4.
Slide the new battery carefully into shaft of the UPS until 
the  end.  Mount  the  bracket  for  fixing  the  battery  pack 
and  connect  the  system  electrically.  Push  the  contact 
together  quickly  and  firmly.  Take  care  of  the  right 
polarity ( red - red / black - black)