Maintenance
The  PROTECT B.  consists  of  advanced  and  resistant 
components. To guarantee a continuous and high availability it is 
recommended to check the unit (especially the batteries and the 
fans) in regular intervals (at least every 6 months).
CAUTION:
Follow safety and security regulations 
unconditionally!
Visual control
When going through the visual control check whether:
mechanical  defects  or  foreign  matter  is  visible  in  the 
system
conducting dirt or dust sediments are in the unit and
dust  sediments  prevent  optimal  ventilation  in  and  out 
the unit.
CAUTION:
Before going through the next step disconnect 
the PROTECT B. from the mains.
If  the  unit  is  very  dusty  it  is  recommended  to  clean  the  UPS 
with compressed air to enable optimal ventilation. 
The time intervals for the visual control depend mainly on the 
local situation at the deployment site. 
Battery control
The  aging  process  can  be  detected  by  regular  capacity 
probes. Make comparison measurements every 12 month e.g. 
by simulating a power failure and check how long the standby 
time  lasts.  The  load  should  always  be  the  same  for  each 
simulation.  Dramatic  changes  compared  to  the  last 
measurements  require  a  change  of  batteries.  Contact  your 
local dealer or call our hotline (see page 4).