Minuteman UPS CPE 1000 ユーザーズマニュアル

ページ / 17
 
28
MODEL 
CPE 1000 
CPE 1000i 
CPE 2000 
CPE 2000i 
CPE 3000 
CPE 3000i 
PROTECTION 
Overload 
100%~120% delay 60-seconds before switching to 
Bypass Mode. 
120%~150% delay 10-seconds before switching to 
Bypass Mode. 
>150% immediately switches to Bypass Mode. 
Short-Circuit a) 
Inverter Mode: UPS shuts down. 
b) Bypass Mode: AC Input fuse opens. 
Overheat 
a)  Utility Normal: Switch to Bypass Mode.   
b)  Utility Abnormal: Alarm sounds continuously, 
Fault LED illuminates then the output turns off. 
Brownout, Blackout, 
Overvoltage 
Switches to the Battery Mode. 
Battery Low 
Alarm continuous, until Low Battery Cut-Off 
Noise Suppression 
Comply with EN50091-2. 
 
Spike Suppression 
Comply with EN61000-4-5. 
ALARM 
 
Audible and Visual  Line Failure, Battery Low, Bypass, Overload, Fault.
PHYSICAL 
Dimensions Net 
(WxHxD) 
5.8x8.78x15.8 inch 
(147x223x401 mm) 
5.1x14.4x18.9 inch 
(130x365x479 mm) 
7.5x14.4x17.8 inch 
(190x365x453 mm) 
Weight Net 
33.1 Lbs 
15 Kgs 
59.5 Lbs 
27 Kgs 
79.4 Lbs 
36 Kgs 
Dimensions 
Shipping 
(WxHxD)
 
12.2x15.35x22.1 inch 
(310x390x560 mm) 
11.4x20.1x24.8 inch
(290x510x630 mm) 
13.4x24.8x24.1 inch
(340x630x610 mm) 
 
Weight Shipping 
 
40 Lbs 
18 Kgs 
71 Lbs 
32 Kgs 
84 Lbs 
38 Kgs 
ENVIRONMENT 
Operating Temp 
0 to 40
°C (+32 to +104°F) 
Storage Temp 
-15 to +45
°C (+5 to +113°F) 
Operating/Storage 
Humidity 
30 to 90% Non-Condensing 
Operating Elevation 
0 to 3,000m (0 to +10,000 ft) 
Storage Elevation 
0 to 15,000m (0 to +50,000 ft) 
 
Audible Noise 
<45 dBA at 1 meter (3 ft) 
SAFETY CONFORMANCE 
Safety Standard 
EN50091-1, UL1778, CSA 22.2 (cUL) 
EMC Standard 
EN50091-2, EN61000-3-3, EN61000-3-2, 
FCC Class A 
 
Marks CE, 
cUL 
Specifications are subject to change without prior notice. 
 
29
A.2. Obtaining Service 
 
If the UPS requires Service: 
 
1.Use the TROUBLESHOOTING section to eliminate obvious causes. 
2.Verify there are no circuit breakers tripped.  A tripped circuit breaker is 
the most common problem. 
3.Call your dealer for assistance.    If you cannot reach your dealer, or if they 
cannot resolve the problem call or fax MINUTEMAN Technical Support at 
the following numbers; Voice phone (972) 446-7363, FAX line (972) 446-
9011 or visit our Web site at www.minutemanups.com the "Discussion 
Board".  Please have the following information available BEFORE calling 
the Technical Support Department.   
  A. Your name and address. 
  B. Where and when the unit was purchased. 
  C. All of the model information about your UPS. 
  D. Any information on the failure, including LEDs that may be illuminated. 
  E. A description of the protected equipment, including model numbers if 
possible. 
  F. A technician will ask you for the above information and, if possible, help 
solve your problem over the phone.  In the event that the unit requires 
factory service, the technician will issue you a Return Material Authorization 
Number (RMA #). 
  G. If the UPS is under warranty, the repairs will be done at no charge.    If 
not, there will be a charge for repair. 
4. Pack the UPS in its original packaging.  If the original packaging is no 
longer available, ask the Technical Support Technician about obtaining a 
new set.    It is important to pack the UPS properly in order to avoid damage 
in transit.    Never use Styrofoam beads for a packing material. 
  A. Include a letter with your name, address, daytime phone number, RMA 
number, a copy of your original sales receipt, and a brief description of the 
problem. 
5. Mark the RMA # on the outside of all packages.  The factory cannot 
accept any package without the RMA # marked on the outside. 
6. Return the UPS by insured, prepaid carrier to: 
 
Para Systems Inc. 
MINUTEMAN UPS 
1455 LeMay Drive 
Carrollton, TX 75007 
ATTN: RMA # _______