Minuteman UPS CPE 1000 ユーザーズマニュアル

ページ / 17
 
10
2.2.2 Terminal Block Explanation 
 
For 3K Tower Type 230V Only 
 
 
 
2.3 Communication Port and PP Contact Card Explanation   
 
The communication port on the rear panel of the UPS is a true RS232 serial 
type. It may be connected to a computer and allows the computer to monitor 
the status of UPS, and control the operation of the UPS, via the Power 
Monitoring software.  The Power Monitoring Software is for the Windows 
environment, such as Windows 3.1, Windows 95 & 98, Windows NT.    For 
other applications, such as Novell NetWare, Unix, etc., please contact your 
local distributor for a proper solution.   
 
2.3.1. The RS232 Interface Settings 
 
 
 
 
 
 
2.3.2. The Pin Assignments of the RS232 Port 
 
 
 
 
 
 
 
 
 
 
 
Baud Rate 
: 2400 bps 
Data Length  : 8 bits 
Stop Bit 
: 1 bit 
Parity 
: None 
1
2
3
4
5
6
7
8
9
 
Pin 6: RS232 RXD 
Pin 7: Ground 
Pin 9: RS232 TXD 
 
11
2.3.3. The Pin Assignments of PP Contact Card
 
 
Pin 1: UPS Shutdown, RS232 Input (+3.3 ~ +25VDC/5-seconds) 
Pin 2: Line Fail Signal RS232 Output (Low to High) 
Pin 3: Line Fail Signal Normally Open (40VDC/25mA) 
Pin 4: Common 
Pin 5: Low Battery Signal Normally Open (40VDC/25mA) 
Pin 6: Line Fail Signal Normally Closed (40VDC/25mA) 
Pin 7: Reserved 
Pin 8: Reserved 
Pin 9: Common 
 
Chapter Three: Installation and Operation 
 
The packing condition and the external outlook of the unit should be 
inspected carefully before installation.  Retain the packing material for 
future use. 
 
3.1. Unpacking 
 
1.  Take the UPS out of the PE foam. 
2.  Unwrap the UPS. 
a.  Use the appropriate number of personnel when unpacking and 
lifting the unit. 
b.  The plastic bag holding the UPS is very slippery so be careful in 
unpacking and handling the unit. 
3.  Standard Package includes:   
a. User's 
Manual 
b.  Quick Install Instructions 
c.  Input Power Cord 
d.  IEC output cables (for the 230V models with IEC receptacles) 
e.  RJ11 Phone Cable 
f.  Power Monitoring Software Kit (Includes RS232 Cable) 
 
3.2. Selecting Installation Position   
 
The CPE On-Line Series is intended to be install in a temperature controlled 
environment that is free of conductive contaminants.  Select a location, which 
will provide good air circulation for the UPS.  Avoid locations near heating 
devices, water or excessive humidity, or where the UPS is exposed to direct 
sunlight.    Route power cords so they cannot be walked on or damaged. 
 
Operating Temperature (Max):    0 to 40 degrees C (+32 to +104 degrees F) 
Operating Elevation:    0 to 3,000m (0 to +10,000 ft) 
Operating and Storage Relative Humidity:    30 - 90%, non-condensing 
Storage Temperature:    -15 to +45 degrees C (+5 to +113 degrees F) 
Storage Elevation:    0 to 15,000m (0 to +50,000 ft)