Minuteman UPS CPE 1000 ユーザーズマニュアル

ページ / 17
 
6
1.1.  The General Characteristics   
 
•  True On-Line architecture continuously supplies your critical device with 
a stable, regulated, transient-free, pure sine wave AC Power. 
•  50KHz PWM sine wave topology yields an excellent overall performance.     
•  The high crest factor of the inverter handles all high-inrush current loads 
without a need to upgrade the power rating.   
•  To protect the unit from overloading, it automatically switches to Bypass 
mode in case loading exceeds 120% of rating.  It will automatically 
switch back to On-Line mode once overload condition is removed.   
•  Should the unit become overheated, the internal thermistor will detect 
the heat and switch to the Bypass mode and vice versa.   
•  Maintenance-free sealed-type battery minimizes service.   
 
1.2.  The Advanced Technical Characteristics 
 
•  Market leading light and compact design. 
•  Powerful CPU integrates all power stages, control and communication 
functions necessary for maximized UPS protection and functionality, 
including Power management status monitoring, configuration setting, 
operation scheduling, remote control and self-diagnosis.   
•  Advanced CPU communication design allows full function remote 
control from any computer environment via the standard RS232 
interface. 
•  State-of-the-Art IGBT Technology and Industrial Grade quality ensures 
the highest efficiency and reliability under the worst operating condition.   
•  Industry leading inverter protection technology incorporates 2-stage 
output Current sensor, smart overload output current control, improved 
crest factor, and feedback fail proof circuit. 
•  Guarantees an exclusive protection against DC damage for inductive 
load, such as motor-based devices. 
•  Advanced Input PFC control guarantees the PF performance and 
maximum energy efficiency. 
•  Unique electronic over-current protection detects output short-circuit and 
faults, and halts the output before damages are done to the output fuse 
or the equipment. 
•  Expanded input voltage range minimizes battery usage and maximizes 
battery life.   
•  Automatic Frequency Sensor reduces the frequency shift. 
•  DC-start function allows the UPS to operate when there is no input 
power available. 
•  On-demand self-diagnosis function ensures UPS reliability. 
•  SNMP adapter slot allows power management and diagnostics via the 
Internet from any where in the world. 
•  User adjustable output voltages for your critical equipment. 
 
7
1
1
1
2
2
2
3
3
3
4
4
4
5
6
5
6
5
6
7
7
7
8
8
8
9
9
9
2KVA
3KVA
1KVA
Chapter Two: 
 
Introduction to the Front and Rear Panel
 
2.1.  Front Panel Display Explanation 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1.  Main Switch 
This is to turn the UPS on/off. 
2.  Self-Test OK 
LED 
Green LED illuminates if the self-test is O.K. 
3.  Test/Silence 
a. Alarm Silence. 
b.1.For Standard Unit:  Self-Test.  Press the 
button over 10 sec. 
b.2.For Unit with Manual Bypass 
function(Special order required):    Press the 
button over 5 seconds, the UPS will be switched 
to Bypass mode and vice versa. 
c. Displays the percentage of output load level in 
AC Mode, and the battery capacity in the Battery 
Mode. 
4.  Fault LED 
Red LED illuminates if the UPS detects an 
Internal Fault. 
5.  Bypass LED 
Amber LED illuminates when UPS is in Bypass 
mode. 
6.  Utility LED 
a. AC normal: Green LED illuminates. 
b. 100% for load levels & battery capacity. 
7.  Inverter LED 
a. Inverter On: Green LED illuminates. 
b. 75% for load levels & battery capacity. 
8.  Low Battery 
Warning LED 
a. Battery Low: Red LED illuminates. 
b. 50% for load levels & battery capacity. 
9.  Overload LED 
a. Overload condition: Red LED illuminates. 
b. 25% for load levels & battery capacity.