Maintenance Object Repair Procedures 
Page 10-1190
STRAT-3 (Stratum 3 Clock)] 
10
reinserted, and the cable between the Stratum 3 clock and the 
TN780 Tone-Clock circuit pack should be replaced. If Test #651 
continues to fail, then escalate the problem.
c. This error indicates that the Tone/Clock circuit pack in the master port 
network is not a TN780 Tone/Clock circuit pack when a Stratum 3 clock is 
administered. Verify that the Tone/Clock in the master port network is 
TN780.
d. This error indicates that the Stratum 3 clock has either reference A or CI 
card A failed. Please refer to the error code 1 in the test description of the 
Test #649 for the repair procedure.
e. This error indicates that the Stratum 3 clock has one power supply failed. 
Please refer to the error code 2 in the test description of the Test #649 for 
the repair procedure.
f. This error indicates that the Stratum 3 clock has one clock unit failed. 
Please refer to the error code 4 in the test description of the Test #649 for 
the repair procedure.
g. This error indicates that the Stratum 3 clock has either reference B or CI 
card B failed. Please refer to the error code 8 in the test description of the 
Test #649 for the repair procedure.
h. This error indicates that the Stratum 3 clock has all power supplies failed. 
Please refer to the error code 16 in the test description of the Test #649 for 
the repair procedure.
i. This error indicates that the Stratum 3 clock has all clock units failed. 
Please refer to the error code 32 in the test description of the Test #649 for 
the repair procedure.
System Technician-Demanded Tests: 
Descriptions and Error Codes
Always investigate tests in the order presented in the following table when 
inspecting errors in the system. By clearing error codes associated with the 
Stratum 3 Clock Alarm Query Test,
 for example, you may also clear errors 
generated from other tests in the testing sequence.
1.
D = Destructive; ND = Nondestructive
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
D/ND
1
Stratum 3 Clock Alarm Query (#649)
X
X
ND