Canon GM-1000 ユーザーズマニュアル

ページ / 140
 
CANON  Digital Galvano Scanner System  GM-1000 Series 
Users Manual 1.20 
 
 
 
  
124
Parameter ID 
64 
Parameter 
Name 
DSP Operation Setting 
Data 
DSP operation setting (Unit: none) 
Return Value  0: Parameter setting successful 
1: Parameter setting unsuccessful 
Explanation 
This parameter is used to set the start up mode. Each bit has a meaning. 
 
Bit 0    0: No automatic encoder correction at homing to the origin 
            1: Automatic encoder correction at homing to the origin 
 
Bit 1    0: Start up in internal clock mode 
      1: Start up in high-speed serial communication (external clock) mode 
 
Bit 2    0: High-speed serial communication specification (XY2-100) (Usually 0) 
 
Note: The setting is decimal. 
Related 
Command 
/Parameter 
 
 
Parameter ID 
66 
Parameter 
Name 
High Speed Serial Status Format 
Data 
High Speed Serial Status Format (Unit: none) 
Return Value  0: Parameter setting successful 
1: Parameter setting unsuccessful 
Explanation 
The content of status output to the status line of high-speed serial communications can 
be selected. 
        0:  Controller Condition 1 
        1:  Controller Condition 2 
        2:  Current position (Axis 1) 
        3:  Current position (Axis 2) 
        4:  Current position (Axis 1 , Axis 2) 
(For details, see 2.8.4. , “Status (High-speed Serial Communication STS)”) 
Related 
Command 
/Parameter 
 
 
Parameter ID 
67 
Parameter 
Name 
High Speed Serial Data Length 
Data 
High Speed Serial Data Length (Unit: bit)      Range = 16 ~ 20 
Return Value  0: Parameter setting successful 
1: Parameter setting unsuccessful 
Explanation 
Position Data length of High-speed serial communication can be specified. 
Range =    16 bit ~ 20 bit 
(For details, see 2.8.3. , “High-speed serial communication”) 
Related 
Command 
/Parameter