4  SYSTEM CONFIGURATION
4.4  Limitation on Current Consumption
49
4
4.
Check if expansion to the CPU module is permitted.
 • 5 V DC power supply
 • 24 V DC power supply
The value obtained by this calculation (when the value is positive) indicates the remaining capacity of 24 V DC service power 
supply, and the capacity can be used for external loads.
If the calculation result is a negative value, the current consumption exceeds the power supply capacity of the CPU module.
Reconfigure the system, adding powered input/output module or extension power supply modules.
Power supply check from the powered input/output module 
(current consumption calculation)
If 24 V DC and 5 V DC power supplies of the CPU module are insufficient and system cannot be extended, add a powered 
input/output module.
Check if power can be supplied to extension modules with the power supply capacity of the powered input/output module.
Calculate following the procedure below.
1.
Check the power supply capacity of the powered input/output module.
*1 Value when service power supply is used for input circuits.The power supply capacity differs when external power supply is used for 
input circuit.
Type
Model
Power supply capacity
5 V DC power supply
24 V DC service power supply
Powered input/output module
FX5-32ER/ES
965 mA
250 mA
mA
-
mA
CPU module
Current consumption
mA ≥
0 mA
=
Calculation result
Ex.
510 mA
900 mA
390 mA
Capacity of 5 V DC 
power supply
Total of current 
consumed by extension 
module
mA
-
mA
CPU module
Current consumption
mA ≥
0 mA
=
Calculation result
Ex.
240 mA
400 mA
160 mA
Capacity of 24 V DC 
power supply
Total of current 
consumed by extension 
module
CPU module
Expansion
adapters
Expansion
board
Output
module
Input
module
Output
module
Input
module
FX5
Intelligent
module
FX3
Intelligent
module
Powered 
input/
output
module
Power supply from powered input/output module
Bus
conversion
module
Ex.