Mitsubishi Electronics FR-A701 ユーザーズマニュアル

ページ / 259
104
Ac
celerat
ion/
d
ecelera
tion t
ime 
set
ting
7

Acceleration time
0.1/
0.01s
0 to 3600/
360s
Set the motor acceleration time.
* The initial value differs according to the inverter
capacity. (7.5K or lower/11K or higher) 
8

Deceleration time
0.1/
0.01s
5/15s
0 to 3600/
360s
Set the motor deceleration time.
* The initial value differs according to the inverter
capacity. (7.5K or lower/11K or higher) 
20
Acceleration/deceleration 
reference frequency
0.01Hz
60Hz
1 to 400Hz
Set the frequency referenced as acceleration/
deceleration time.  Set the frequency change time 
from stop to Pr. 20 for acceleration/deceleration time.
21
Acceleration/deceleration 
time increments
1
0
0
Increments: 0.1s
Range: 0 to 3600s
The increments and 
setting range of 
acceleration/deceleration 
time setting can be 
changed.
1
Increments: 0.01s
Range: 0 to 360s
44
Second acceleration/
deceleration time
0.1/
0.01s
5s
0 to 3600/
360s
Set the acceleration/deceleration time when the RT 
signal is on.
45
Second deceleration time
0.1/
0.01s
9999
0 to 3600/
360s
Set the deceleration time when the RT signal is on.
9999
Acceleration time = deceleration time
110
Third acceleration/
deceleration time
0.1/
0.01Hz
9999
0 to 3600/
360s
Set the acceleration/deceleration time when the X9 
signal is on.
9999
Function invalid
111
Third deceleration time
0.1/
0.01Hz
9999
0 to 3600/
360s
Set the deceleration time when the X9 signal is on.
9999
Acceleration time = deceleration time
Mot
o
r prot
ect
ion 
fr
om overh
eat
 
(elect
ronic t
h
e
rmal 
re
la
y fu
n
ctio
n
)
9

Electronic thermal O/L relay
0.01A
Rated 
inverter  
current
 0 to 500A Set the rated motor current.
51
Second electronic thermal 
O/L relay
0.01A
9999
0 to 500A
Valid when the RT signal is on.
Set the rated motor current.
9999
Second electronic thermal O/L relay invalid
DC injec
tion brak
e
10
DC injection brake operation 
frequency
0.01Hz 3/0.5Hz
0 to 120Hz
Operation frequency of the DC injection brake.
* The initial value changes from 3Hz to 0.5Hz when a
control mode other than vector is changed to vector
control.
9999
Operate when the output frequency becomes less 
than or equal to Pr. 13 Starting frequency.
11
DC injection brake 
operation time
0.1s
0.5s
0
DC injection brake disabled
0.1 to 10s
Operation time of the DC injection brake
8888
Operated while the X13 signal is on.
12
DC injection brake 
operation voltage
0.1%
4/2% 
0
DC injection brake disabled
0.1 to 30%
DC injection brake voltage (torque)
* The initial value differs according to the inverter
capacity. (7.5K or lower/11K or higher)
802
Pre-excitation selection
1
0
0
Zero speed control
Setting can be made under 
vector control.
1
Servo lock
850
Brake operation selection
1
0
0
DC injection brake
1
Zero speed control (under Real sensorless vector 
control)
2
Magnetic flux decay output shutoff (under Real 
sensorless vector control)
S
tart
ing 
fr
e
quency
13
Starting frequency
0.01Hz
0.5Hz 0 to 60Hz
Starting frequency 
571
Holding time at a start
0.1s
9999
0.0 to 10.0s Holding time of Pr. 13 Starting frequency.
9999
Holding function at a start is invalid
Func
tio
n
Parameter
Name
Incre
ments
Initial 
Value
Range
Description
Re
la
te
d
 
p
ara
m
e
te