Mitsubishi Electronics FR-V540-1.5K to 55K ユーザーズマニュアル

ページ / 232
124
Offline auto tuning (Pr. 80 to Pr. 96)
3.12.5 Setting the motor constants directly
Offline auto tuning is not used.
The Pr. 92 and Pr. 93 motor constants may either be entered in [
Ω] or in [mH]. Before starting operation, confirm 
which motor constant unit is used
.
 (Refer to page 120.)
z To enter the Pr. 92 and Pr. 93 motor constants in [Ω]
<Operating procedure>
1. After checking that the input motor constants are those for star connection or delta connection, set the Pr. 71
value as indicated below (When direct input is selected and offline auto tuning is performed, set "7, 8, 17 or 18") 
in Pr. 71. (Refer to page 125.).
2. Set "801" in Pr. 77.
 
(The parameter values of the motor constants (Pr. 90 to Pr. 94) can be displayed. Though the parameter values 
of other than Pr. 90 to Pr. 94 can also be displayed, they are parameters for manufacturer setting and their 
values should not be changed.)
3. In the parameter setting mode, read the following parameters and set desired values.
4. Return the Pr. 77 setting to the original value.
5. Set Pr. 83 and Pr. 84.
z To enter the Pr. 92 and Pr. 93 motor constants in [mH]
<Operating procedure>
1. After checking that the input motor constants are those for star connection or delta connection, set the Pr. 71
value as indicated below.
2. Set "801" in Pr. 77.
 
(The parameter values of the motor constants (Pr. 90 to Pr. 94) can be displayed. Though the parameter values 
of other than Pr. 90 to Pr. 94 can also be displayed, they are parameters for manufacturer setting and their 
values should not be changed.)
Star Connection Motor Delta Connection Motor
Pr. 71
Setting
Standard motor
5
6
Constant-torque motor
15
16
Parameter Number
Name
Setting Range Setting Increments Factory Setting
82
Motor excitation current (no load current)
0 to 500A
0.01A
9999
90
Motor constant r1
0 to 50
Ω, 9999
0.001
Ω
9999
91
Motor constant r2
0 to 50
Ω, 9999
0.001
Ω
9999
92
Motor constant x1
0 to 50
Ω, 9999
0.001
Ω
9999
93
Motor constant x2
0 to 50
Ω, 9999
0.001
Ω
9999
94
Motor constant xm
0 to 500
Ω, 9999
0.01
Ω
9999
859
Torque current
0 to 500A
0.01A
9999
Parameter Number
Name
Setting Range Setting Increments Factory Setting
83
Rated motor voltage
0 to 1000V
0.1V
200V/400V
84
Rated motor frequency
10 to 200Hz
0.01Hz
60Hz
CAUTION
1. Set "9999" in Pr. 90 to Pr. 94 to use the standard motor constants (including those for the constant-
torque motor).
2. If "star connection" is mistaken for "delta connection" or vice versa during setting of Pr. 71, control 
cannot be exercised properly.
Pr. 71
Setting
Standard motor
0
Constant-torque motor
10
SF-V5RU
30
Iq=Torque, I
100
=Rated current, I
0
=No load current