Online auto tuning (Pr. 95)
3.13 Online auto tuning (Pr. 95)
3.13.1 Online auto tuning selection
 
(Pr. 95, Pr. 9, Pr. 71, Pr. 80, Pr. 81 
)
(1) Pr. 95 = "1" (start time tuning)
The current at a start is detected to compensate for the secondary resistance of the motor so that excellent 
characteristics are provided regardless of the change in value of the secondary resistance of the motor with the rise 
of the motor temperature.
Excellent torque accuracy is provided by temperature compensation even if the secondary resistance value of 
the motor varies with the rise in the motor temperature.
Parameter
Name
Factory Setting
Setting Range
Remarks
95
Online auto tuning 
selection
0
0, 1, 2
0: Online auto tuning not performed
1: Start time tuning (at start-up)
2: Adaptive magnetic flux observer (normal)
9
Electronic thermal 
 
O/L relay
0A
0 to 500A
Used as rated motor current and electronic 
thermal relay function parameters.
71
Applied motor
30
Refer to page 111 and make setting.
80
Motor capacity
Inverter capacity
0.4 to 55kW
(Down to one rank lower than the inverter 
capacity)
81
Number of motor poles
4
2, 4, 6
CAUTION
1. Perform offline auto tuning in the rotation mode before performing online auto tuning with start time 
tuning. Data needs to be calculated.
2. For using start time tuning in vertical lift applications, examine the utilization of a brake sequence for 
the brake opening timing at a start. Though the tuning ends in about a maximum of 500ms after a 
start, torque is not provided fully during that period. Therefore, note that there may be a possibility of 
drop due to gravity.
REMARKS
To prevent delay at starting, X28 function which executes tuning before start signal input is provided. (Refer to page 33.)
speed
torque