Display function 3 (Pr. 160)
3.18 Display function 3 (Pr. 160)
3.18.1 Extended function display selection (Pr. 160
)
3.19 Initial monitor (Pr. 171)
3.19.1 Actual operation hour meter clear (Pr. 171
)
<Setting>
Write "0" in the corresponding parameter to clear the actual operation hour.
3.20 Terminal assignment functions (Pr. 180 to Pr. 195)
3.20.1 Input terminal function selection 
 
(Pr. 180 to Pr. 183, Pr. 187
)
Used to display the extended function parameters.
z Refer to page 66 for the extended function parameter list.
Parameter
Name
Factory 
Setting
Setting 
Range
Remarks
160
Extended function 
selection
0
0
Only the simple mode parameters are accessible.
1
All parameters are accessible.
Pr. 162 to Pr. 165
Refer to Pr. 57 (page 101).
You can clear the actual operation hour of the monitoring function.
Parameter
Name
Factory Setting
Setting Range
171
Actual operation hour 
meter clear
0
0
REMARKS
The actual operation time is the value monitored by setting "23" in Pr. 52.
Related parameters
• Pr. 52 "DU/PU main display data selection" (Refer to page 97.)
Use these parameters to select/change the input terminal functions.
Parameter
Name
Terminal 
Symbol
Factory-
Set Value
Factory-Set Terminal 
Function
Setting 
Range
Remarks
180
DI1 terminal 
function 
selection
DI1
0
Low speed operation 
command (RL)
0 to 3, 5, 8 to 
12,14 to 16, 
20, 22 to 28, 
42 to 44, 
9999
9999: No function
Extended 
mode
181
DI2 terminal 
function 
selection
DI2
1
Middle speed 
operation command 
(RM)
182
DI3 terminal 
function 
selection
DI3
2
High speed operation 
command (RH)
183
DI4 terminal 
function 
selection
DI4
3
Second function/
second motor 
switchover (RT)
187
STR 
terminal 
function 
selection
STR
9999
Reverse rotation 
command (STR)
9999: STR
speed
torque position
speed
torque position
speed
torque
position