3.4.22 Initial settings and specifications of RS-485 communication (Pr. 117 to Pr. 124)
[Parameters related to PU connector communication]
This function is used to perform required settings for RS-485 communication between the converter and personal
computer.
Use PU connector of the converter for communication.
You can perform parameter setting, monitoring, etc. using Mitsubishi inverter protocol.
To make communication between a personal computer and a converter, initialization of the communication
specifications must be made to the converter.
Data communication cannot be made if the initial settings are not made or there is any setting error.
Parameter 
Number
Name
Initial 
Value
Setting Range
Description
117
PU communication station number
0
0 to 31
Converter station number specification
Set the converter station numbers when two or more 
converters are connected to one personal computer.
118
PU communication speed
192
48, 96, 192, 384
Set the communication speed.
The setting value 
 100 equals the communication 
speed.
For example, if 192 is set, the communication speed is 
19200bps. 
119
PU communication stop bit length
1
Stop bit length
Data length
0
1bit
8 bits
1
2  bits
10
1bit
7 bits
11
2 bits
120
PU communication parity check
2
0
Without parity check
1
With parity check at odd numbers
2
With parity check at even numbers
121
Number of PU communication 
retries
1
0 to 10
Set the permissible number of retries for unsuccessful 
data reception. If it is still unsuccessful after the 
permissible number of retries, the converter stops 
retrying  communication.
9999
The converter does not retry communication even when 
the communication is unsuccessful.
123
PU communication waiting time 
setting
9999
0 to 150ms
Set the waiting time between data transmission to the 
converter and the response.
9999
Set with communication data.
124
PU communication CR/LF selection
1
0
Without CR/LF
1
With  CR
2
With  CR/LF
NOTE
Always reset the converter after making the initial settings of the parameters. After you change the communication-
related parameters, communication cannot be made until the converter is reset.