Monitor display and monitor output signal
4
4.11 Monitor display and monitor output signal
4.11.1 Speed display and speed setting (Pr. 37, Pr. 144, Pr. 505)
...... The specification differs according to the manufacture date. Refer to page 400 and check the SERIAL. 
*1
The maximum value of the setting range differs according to the Pr.1 Maximum frequency and it can be calculated from the following formula.
Note that Pr.37 (set maximum value) is 9998 if the result of the above formula exceeds 9998.
*2
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
⋅ To display the machine speed, set in Pr. 37 the machine speed for operation with frequency set in Pr. 505.
For example, when Pr. 505 = "60Hz" and Pr. 37 = "1000", "1000" is displayed on the running speed monitor when the
running frequency is 60Hz. When running frequency is 30Hz, "500" is displayed.
⋅ When displaying the motor speed, set the number of motor poles (2, 4, 6, 8, 10) or number of motor poles + 100
(102, 104, 106, 108, 110) to Pr. 144.
⋅ When both Pr. 37 and Pr. 144 have been set, their priorities are as given below.
Pr. 144, 102 to 110
 > Pr. 37, 1 to 9998 > Pr. 144, 2 to 10
⋅ When the running speed monitor is selected, each monitor and setting are determined by the combination of Pr. 37
and Pr. 144 as listed below. (The units within the thick frame are the initial values.)
Purpose
Parameter that must be set
Refer to 
Page
Display motor speed
Set speed
Speed display and speed setting
Pr. 37,  Pr. 144,  Pr. 505
Change PU monitor display data
DU/PU main display data selection
Cumulative monitor clear
Pr. 52,  Pr. 170,  Pr. 171, 
Pr. 268, Pr. 891
Change of the monitor output from 
terminal CA and AM
Terminal CA, AM function selection
Pr. 54, Pr. 158, Pr. 867, Pr. 869
Set the reference of the monitor 
output from terminal CA and AM
Setting of reference of terminal CA and AM
Pr. 55, Pr. 56,  Pr. 867
Adjust terminal CA, AM outputs
Terminal CA, AM calibration
Pr. 900, Pr. 901, Pr. 930, Pr. 931
You can change the PU (FR-DU07/FR-PU04/FR-PU07) monitor display or frequency setting to motor speed or
machine speed.
Parameter 
Number
Name
Initial Value
Setting Range
Description
37
Speed display
0
0
Frequency display, setting
1 to 9998 
*1
Set the machine speed at 60Hz.
144
Speed setting switchover
4
0, 2, 4, 6, 8, 10, 102, 
104, 106, 108, 110
Set the number of motor poles when 
displaying the motor speed.
505
Speed setting reference
60Hz
1 to 120Hz
Set the reference speed for Pr. 37.
Pr.37 (set maximum value) 
<
65535 x Pr.505
Pr.1(Hz)
Pr. 37
Setting
Pr. 144
Setting
Output Frequency 
Monitor
Set Frequency 
Monitor
Running Speed 
Monitor
Frequency Setting 
Parameter Setting
0
(initial 
value)
0
Hz
Hz
r/min 
Hz
2 to 10
Hz
Hz
r/min 
Hz
102 to 110
r/min 
r/min 
r/min 
r/min 
1 to 9998
0
Hz
Hz
Machine speed 
Hz
2 to 10
Machine speed 
Machine speed 
Machine speed 
Machine speed 
102 to 110
Hz
Hz
r/min  
Hz
*1
Motor speed r/min conversion formula............ frequency 
× 120/number of motor poles (Pr. 144)
Machine speed conversion formula...................Pr. 37 
× frequency/Pr. 505 setting (Hz)
For Pr. 144 in the above formula,  the value is "Pr. 144-100" when  "102 to 110" is set in Pr. 144 and the value is "4" when Pr. 37 = 0 and Pr. 144 = 0. 
*2
The increments for Hz are 0.01Hz, machine speed are 1m/min, and r/min are 1r/min.
*3
Pr. 505 is always set as frequency (Hz).