Monitor display and monitor output signal
4
4.11.2 DU/PU monitor display selection 
(Pr. 52, Pr. 54, Pr. 158, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891)
The monitor to be displayed on the main screen of the operation panel (FR-DU07)/parameter unit (FR-PU04/FR-
PU07) can be selected.
Parameter 
Number
Name
Initial Value
Setting Range
Description
52 *
DU/PU main display data 
selection
0
(output 
frequency)
0, 5, 6, 8 to 14, 
17, 20, 23 to 25, 
50 to 57, 67, 
81 to 86 100
Select the monitor to be displayed on the 
operation panel and parameter unit.
Refer to the following table for monitor description.
54 *
CA terminal function 
selection
1
(output 
frequency)
1 to 3, 5, 6, 
8 to 14, 17, 21, 
24, 50, 52, 53, 
67, 70, 85
Select the monitor output to terminal CA.
158 *
AM terminal function 
selection
1 to 3, 5, 6, 
8 to 14, 17, 21, 
24, 50, 52, 53, 
67, 70, 86
Select the monitor output to terminal AM.
170
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter monitor.
10
Sets the maximum value for the monitoring from 
communication to 9999kWh.
9999
Sets the maximum value for the monitoring from 
communication to 65535kWh.
171
Operation hour meter clear
9999
0, 9999
Set "0" to clear the operation time monitor.
Setting "9999" has no effect.
268 *
Monitor decimal digits 
selection
9999
0
Displayed as integral value.
1
Displayed in 0.1 increments.
9999
No function
563
Energization time 
carrying-over times
0
0 to 65535
(reading only)
Displays the numbers of cumulative energization 
time monitor exceeded 65535h. Reading only
564
Operating time carrying-
over times
0
0 to 65535
(reading only)
Displays the numbers of operation time monitor 
exceeded 65535h. Reading only
891 *
Cumulative power monitor 
digit shifted times
9999
0 to 4
Set the number of times to shift the cumulative 
power monitor digit.
Clamps the monitor value at maximum.
9999
No shift
Clears the monitor value when it exceeds the 
maximum value.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection.
...