Monitor display and monitor output signal
4
4.11.2 DU/PU monitor display selection
(Pr. 52, Pr. 54, Pr. 158, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891)
The monitor to be displayed on the main screen of the operation panel (FR-DU07)/parameter unit (FR-PU04/FR-
PU07) can be selected.
PU07) can be selected.
Parameter
Number
Name
Initial Value
Setting Range
Description
52 *
DU/PU main display data
selection
selection
0
(output
frequency)
0, 5, 6, 8 to 14,
17, 20, 23 to 25,
50 to 57, 67,
81 to 86 100
81 to 86 100
Select the monitor to be displayed on the
operation panel and parameter unit.
Refer to the following table for monitor description.
operation panel and parameter unit.
Refer to the following table for monitor description.
54 *
CA terminal function
selection
selection
1
(output
frequency)
1 to 3, 5, 6,
8 to 14, 17, 21,
24, 50, 52, 53,
67, 70, 85
Select the monitor output to terminal CA.
158 *
AM terminal function
selection
selection
1 to 3, 5, 6,
8 to 14, 17, 21,
24, 50, 52, 53,
67, 70, 86
Select the monitor output to terminal AM.
170
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter monitor.
10
Sets the maximum value for the monitoring from
communication to 9999kWh.
communication to 9999kWh.
9999
Sets the maximum value for the monitoring from
communication to 65535kWh.
communication to 65535kWh.
171
Operation hour meter clear
9999
0, 9999
Set "0" to clear the operation time monitor.
Setting "9999" has no effect.
Setting "9999" has no effect.
268 *
Monitor decimal digits
selection
selection
9999
0
Displayed as integral value.
1
Displayed in 0.1 increments.
9999
No function
563
Energization time
carrying-over times
carrying-over times
0
0 to 65535
(reading only)
Displays the numbers of cumulative energization
time monitor exceeded 65535h. Reading only
time monitor exceeded 65535h. Reading only
564
Operating time carrying-
over times
over times
0
0 to 65535
(reading only)
Displays the numbers of operation time monitor
exceeded 65535h. Reading only
exceeded 65535h. Reading only
891 *
Cumulative power monitor
digit shifted times
digit shifted times
9999
0 to 4
Set the number of times to shift the cumulative
power monitor digit.
Clamps the monitor value at maximum.
power monitor digit.
Clamps the monitor value at maximum.
9999
No shift
Clears the monitor value when it exceeds the
maximum value.
Clears the monitor value when it exceeds the
maximum value.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection.
...
Specifications differ according to the date assembled. Refer to page 400 to check the SERIAL number.