Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
177
Frequency setting by analog input (terminal 1, 2, 4)
4
4.16.4 Bias and gain of frequency setting voltage (current) 
(Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) to C7(Pr. 905))
You can set the magnitude (slope) of the output frequency as desired in relation to the frequency setting signal (0
to 5V, 0 to 10V or 4 to 20mADC).
Set Pr. 73 and Pr. 267 to switch between 0 to 5VDC, 0 to 10VDC and 4 to 20mADC. (Refer to page 171)
Parameter 
Number
Name
Initial Value
Setting 
Range
Description
125
Terminal 2 frequency setting gain 
frequency
60Hz
 0 to 400Hz
Set the frequency of terminal 2 input gain 
(maximum).
126
Terminal 4 frequency setting gain 
frequency
60Hz
 0 to 400Hz
Set the frequency of terminal 4 input gain 
(maximum).
241
Analog input display unit 
switchover
0
0
Displayed in %
Select the unit of 
analog input display.
1
Displayed in V/mA
C2(902)
Terminal 2 frequency setting bias 
frequency
0Hz
 0 to 400Hz
Set the frequency on the bias side of 
terminal 2 input.
C3(902)
Terminal 2 frequency setting bias 
0%
 0 to 300%
Set the converted % of the bias side 
voltage (current) of terminal 2 input.
C4(903)
Terminal 2 frequency setting gain
100%
 0 to 300%
Set the converted % of the gain side 
voltage (current)  of terminal 2 input.
C5(904)
Terminal 4 frequency setting bias 
frequency
0Hz
 0 to 400Hz
Set the frequency on the bias side of 
terminal 4 input.
C6(904) 
Terminal 4 frequency setting bias 
20%
 0 to 300%
Set the converted % of the bias side 
current (voltage) of terminal 4 input.
C7(905) 
Terminal 4 frequency setting gain
100%
 0 to 300%
Set the converted % of the gain side 
current (voltage) of terminal 4 input.
*1
The parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190.)
*2
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
*3
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter
write selection.