Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
16
Main circuit terminal specifications
2.2 Main circuit terminal specifications
2.2.1
Specification of main circuit terminal
2.2.2
Terminal arrangement of the main circuit terminal, power supply and the motor 
wiring
200V class
Terminal 
Symbol
Terminal 
Name
Description
Refer 
to 
page
R/L1, 
S/L2, 
T/L3
AC power 
input
Connect to the commercial power supply.
Keep these terminals open when using the high power factor 
converter (FR-HC, MT-HC) or power regeneration common converter 
(FR-CV).
U, V, W
Inverter output Connect a three-phase squirrel-cage motor.
R1/L11, 
S1/L21
Power supply 
for control 
circuit
Connected to the AC power supply terminals R/L1 and S/L2. To 
retain the fault display and fault output or when using the high power 
factor converter (FR-HC, MT-HC) or power regeneration common 
converter (FR-CV), remove the jumpers from terminals R/L1 and R1/
L11, and S/L2 and S1/L21 and apply external power to these 
terminals.
The power capacity necessary when separate power is supplied from 
R1/L11 and S1/L21 differs according to the inverter capacity.  
P/+, N/-
Brake unit 
connection
Connect the brake unit (FR-BU2, FR-BU, BU and MT-BU5), power 
regeneration common converter (FR-CV), high power factor converter 
(FR-HC and MT-HC) or power regeneration converter (MT-RC).
P/+, P1
DC reactor 
connection
For the FR-F720-02330 (FR-F740-01160) or less, remove the jumper 
across terminals P/+ and P1 and connect the DC reactor. (Be sure to 
connect the DC reactor supplied with the FR-F720-03160 (FR-F740-
01800) or more.)
When a DC reactor is not connected, the jumper across terminals P/
+ and P1 should not be removed.
PR, PX
Please do not remove or use terminals PR and PX or the jumper connected. 
-
Earth (ground)
For earthing (grounding) the inverter chassis. Must be earthed 
(grounded).
FR-F720-00046, 00077-NA
FR-F720-00105 to 00250-NA
200V
class
FR-F720-00630 or less
60VA
FR-F720-00770
80VA
FR-F720-00930 or more
80VA
400V
class
FR-F740-00310 or less
60VA
FR-F740-00380
60VA
FR-F740-00470 or more
80VA
R/L1 S/L2 T/L3
N/-
P/+
PR
PX
R1/L11 S1/L21
Charge lamp
As this is an inside cover fixing screw, 
do not remove it.
Jumper
Jumper
Motor
Power supply
IM
R/L1 S/L2 T/L3
N/-
P/+
PR
PX
R1/L11 S1/L21
IM
Charge lamp
Jumper
Jumper
Motor
Power
supply