PID control
4
4.20.4 Second PID function (Pr.753 to Pr. 758, Pr.765 to Pr.769)
When the RT signal is ON and Pr. 753 Second PID action selection 
≠ 9999, PID control is commanded by the
second function parameters.
When Pr. 753 = 9999, normal PID control is performed even if the second functions are valid. 
When the control method is switched from the second PID control to the normal PID control, the integral value is
estimated. The integral value is estimated by calculating the integral term with the output frequency and the P
term. This method is same as when the control method changes to PID control when the frequency reaches the
automatic switchover frequency.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
753
Second PID action 
selection
9999
10, 110 
PID reverse action
Deviation value signal input
(terminal 1 
11, 111 
PID forward action
20, 120 
PID reverse action
Measured value (terminal 4 
Set point (terminal 2 
or Pr. 133)
21, 121 
PID forward action
50 
PID reverse action
Deviation value signal input
(L
ON
W
ORKS
, CC-Link, BACnet)
51 
PID forward action
60 
PID reverse action
Measured value, set point input
(L
ON
W
ORKS
, CC-Link, BACnet)
61 
PID forward action
70 
PID reverse action
Deviation value signal input
(PLC function)
71 
PID forward action
80 
PID reverse action
Measured value, set point input
(PLC function)
81 
PID forward action
90 
PID reverse action
Deviation value signal input
(PLC function)
(Not reflected to the inverter frequency)
91 
PID forward action
100 
PID reverse action
Measured value, set point input
(PLC function)
(Not reflected to the inverter frequency)
101 
PID forward action
9999
Normal PID control is performed regardless of the second PID 
control parameter settings. 
754
Second PID control 
automatic switchover 
frequency
9999
0 to 400Hz
Set the frequency at which the control is automatically 
changed to PID control while the RT signals is ON. 
9999
Without second PID control automatic switchover function
Second PID action set 
point
9999
0 to 100% 
Set the set point for PID control, which is performed while the 
RT signal is ON.
9999
Terminal 2 input is the set point while the RT signal is ON. 
Second PID 
proportional band
100%
0.1 to 1000%
Set the proportional band for PID control, which is performed 
while the RT signal is ON.
If the proportional band is narrow (parameter setting is small),
the manipulated variable varies greatly with a slight change of
the measured value. Hence, as the proportional band narrows,
the response sensitivity (gain) improves but the stability
deteriorates, e.g. hunting occurs. 
Gain Kp = 1/proportional band
9999
Without second proportional band
Second PID integral 
time
1s
0.1 to 3600s
Set the PID integral time for PID control, which is performed 
while the RT signal is ON.
When deviation step is input, time (Ti) is the time required for 
integral (I) action to provide the same manipulated variable as 
proportional (P) action. 
As the integral time decreases, the set point is reached earlier 
but hunting occurs more easily.
9999
Without second integral control
Second PID differential 
time
9999
0.01 to 
10.00s
Set the PID differential time for PID control, which is performed 
while the RT signal is ON.
When deviation lamp is input, time (Td) is the time required to 
provide the manipulated variable of only the proportional (P) 
action. As the differential time increases, greater response is 
made to a deviation change.
9999
Without second differential control