Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
283
PID control
4
4.20.5 Advanced PID function (pump function) (Pr. 554, Pr. 575 to Pr. 591)
PID control function can adjust the volume of water, etc. by controlling a pump. Multiple motors (4 motors
maximum) can be controlled by switching between the inverter-driven operation and commercial power-
driven operation. Use Pr. 579 Motor connection function selection to select switchover operation of the motor. Up
to three auxiliary motors can be connected.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
554
PID signal operation selection
0
0 to 3, 
10 to 13
Select the operation to be performed at 
the detection of upper, lower, and 
deviation limit for the measured value 
input. The operation for PID output 
suspension function can be selected.
575
Output interruption detection 
time
1s
0 to 3600s
The inverter stops operation if the output 
frequency after PID operation remains at 
less than the Pr. 576 setting for longer than 
the time set in Pr. 575.
9999
Without output interruption function
576
Output interruption detection 
level
0Hz
0 to 400Hz
Set the frequency at which the output 
interruption processing is performed.
577
Output interruption cancel level
1000%
900 to 1100%
Set the level (Pr. 577 minus 1000%) to 
release the PID output interruption 
function.
578
Auxiliary motor operation selection
0
0
No auxiliary motor operation
1 to 3
Set the number of auxiliary motors to be 
run
579
Motor connection function 
selection
0
0
Basic system
1
Alternative system
2
Direct system
3
Alternative-direct system
580
MC switching interlock time
1s
0 to 100s
You can set the time until MC switchover 
interlock time when Pr. 579 = "2, 3" is set.
581
Start waiting time
1s
0 to 100s
You can set the time from when the MC is 
switched until it starts when Pr. 579 = "2, 
3". Set this time a little longer than the MC 
switching time.
582
Auxiliary motor connection-time 
deceleration time
1s
0 to 3600/360s
 
You can set the deceleration time for 
decreasing the output frequency of the 
inverter if a motor connection occurs 
under advanced PID control.
9999
The output frequency is not forcibly 
changed.
583
Auxiliary motor disconnection-
time acceleration time
1s
0 to 3600/360s
 
You can set the acceleration time for 
increasing the output frequency of the 
inverter if a motor disconnection occurs 
under advanced PID control.
9999
The output frequency is not forcibly 
changed.
584
Auxiliary motor 1 starting frequency
60Hz
0 to 400Hz
Set the frequency to connect an auxiliary 
motor.
585
Auxiliary motor 2 starting frequency
60Hz
0 to 400Hz
586
Auxiliary motor 3 starting frequency
60Hz
0 to 400Hz
587
Auxiliary motor 1 stopping frequency
0Hz
0 to 400Hz
Set the frequency to open an auxiliary 
motor.
588
Auxiliary motor 2 stopping frequency
0Hz
0 to 400Hz
589
Auxiliary motor 3 stopping frequency
0Hz
0 to 400Hz
590
Auxiliary motor start detection time
5s
0 to 3600s
You can set the delay time until the 
auxiliary motor is started.
591
Auxiliary motor stop detection time
5s
0 to 3600s
You can set the delay time until the 
auxiliary motor is stopped.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
....
Specifications differ according to the date assembled. Refer to page 400 to check the SERIAL number.
*1
Depends on the Pr. 21 Acceleration/deceleration time increments setting. The initial value for the setting range is "0 to 3600s" and the setting
increments is "0.1s".