Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
321
Setting of FR-PU07-01
4
4.24.3 PID set point direct setting menu
The setting menu is used to input the PID set point (Pr. 133, Pr. 755) in simple steps under PID control. 
Pressing 
 while the FR-PU07-01 is in the monitor mode starts the direct setting mode for the PID set point.
(Valid under PID control. If 
 is pressed while the PID control is invalid, the function menu is displayed.)
REMARKS
In the direct setting mode, parameters can be always read or written regardless of the Pr. 77 and Pr. 160 settings.
P I D s e t
 
0. 0
P S I
- - -  S T O P HAND
 
Monitor mode
Function menu
1   M O N I T O R
 
2   P U   O p e r
 
 
3   P r . L i s t 
4   P r . C l e a r
P I D s e t     p n t 1  
S E T       8 0 . 0 P S I
   
FUNC:FUNC  MENU 
Direct setting mode 1 (
Pr. 133)
 
   
 
Direct setting mode 2 (
Pr. 755)
Direct setting mode 1 (
Pr. 133)
PI D s e t   p n t 1
S E T         8 0 . 0 P S I
S ET
0~ 5 0 0
PI D s e t   p n t 2
S ET
0~ 5 0 0
Direct setting mode 2 (
Pr. 755)
Change the value with the numeric keypad.
Writing of the set value is completed.
The setting is applied to the PID action.
Writing of the set value is completed.
The setting is applied to the PID action.
to
to
(Using        /       , change the value.)
(Using        /       , change the value.)
Change the value with the numeric keypad.
S E T       4 0 . 0 P S I
FUNC:FUNC  MENU
4 0 . 0 P S I
S E T         4 0 . 0 P S I
2 0 . 0 P S I
P I D s e t     p n t 2