Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
322
Setting of FR-PU07-01
4.24.4 3-line monitor selection (Pr. 774 to Pr.776)
*1
The monitor is displayed as Pr. 774 = "1," Pr. 775 = "2," and Pr. 776 = "3" when a parameter unit other than FR-DU07 is used. 
*2
The monitor is displayed as Pr. 774 = "1," Pr. 775 = "2," and Pr. 776 = "3" when the monitor selection is valid.
*3
The setting is available when using PLC function. Refer to the FR-F700 PLC function programming manual for details of the PLC function.
For the parameter unit (FR-PU07)/operation panel (FR-DU07), the first, second, and third monitors can be
changed. When using FR-PU07-01, the monitored items, which are set by Pr.774 to Pr.776, can be displayed in
the 3-line monitor. 
The Pr.52 DU/PU main display data selection setting is invalid when Pr.774 to Pr.776 
 
9999. Monitored item names
are displayed during monitoring (Monitor name display in the 3-line monitor is available only for FR-PU07-01). 
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
774
PU/DU monitor 
selection 1
9999
1 to 3, 5, 6, 8 to 
14, 17, 20, 
23 to 25, 40 to 
42, 50 to 57, 
67, 81 to 86, 
100, 9999
Select the monitored item to be displayed on the first monitor 
(first row in the 3-line monitor).
775
PU/DU monitor 
selection 2
Select the monitored item to be displayed on the second 
monitor (second row in the 3-line monitor).
776
PU/DU monitor 
selection 3
Select the monitored item to be displayed on the third monitor 
(third row in the 3-line monitor).
♦ Parameters referred to 
Pr. 52 DU/PU main display data selection   
Pr. 59 Remote function selection   
Pr. 73 Analog input selection  
Pr. 79 Operation mode selection  
Pr. 133 PID action set point   
Pr. 160 User group read selection   
Pr. 178 to Pr. 189 (input terminal function selection)   
Pr. 190 to Pr. 196 (output terminal function selection)   
C2 (Pr. 902) to C7 (Pr. 905)  Frequency setting voltage (current) bias/gain  
C42 (Pr. 934) to C45 (Pr. 935) (PID control)  
Setting
Monitor item
1
Output frequency
2
Output current
3
Output voltage
5
Frequency setting value
6
Running speed
8
Converter output voltage
9
Regenerative brake duty
10
Electronic thermal relay 
function load factor
11
Output current peak value 
12
Converter output voltage peak 
value
13
Input power
14
Output power
17
Load meter
20
Cumulative energization time
23
Actual operation time
24
Motor load factor
25
Cumulative power
40
PLC function user monitor 1 
*3
41
PLC function user monitor 2 
*3
42
PLC function user monitor 3 
*3
50
Power saving effect
51
Cumulative saving power
52
PID set point
53
PID measured value
54
PID deviation
55 
*1
I/O terminal status
56 
*1
Option input terminal status
57 
*1
Option output terminal status
67
PID measured value 2
81
BACnet reception status
82
BACnet token pass counter
83
BACnet valid APDU counter
Setting
Monitor item
84
BACnet communication error 
counter
85
Terminal CA output level
86
Terminal AM output level
100
Set frequency before 
operation
9999 
*2
No selection
Setting
Monitor item
How the monitor is displayed when  
Pr. 759 = "4," Pr. 774 = "52," Pr. 775 = "53," 
and 
Pr. 776 = "54"