Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
326
Parameter copy and parameter verification
4.27.2 Parameter verification
 appears...Why? 
Parameter read error. Perform operation from step 3 again.
 appears...Why? 
Parameter write error. Perform operation from step 8 again.
 and 
 flicker alternately
Appears when parameters are copied between the inverter of FR-F720-02330 (FR-F740-01160) or less and FR-
F720-03160 (FR-F740-01800) or more.
1. Set "0" in Pr. 160 User group read selection.
2. Set the following setting (initial value) in Pr. 989 Parameter copy alarm release.
3. Reset Pr. 9, Pr. 30, Pr. 51, Pr. 52, Pr. 54, Pr. 56, Pr. 57, Pr. 70, Pr. 72, Pr. 80, Pr. 90, Pr. 158, Pr. 190 to Pr. 196, Pr. 557,
Pr. 893.
Whether same parameter values are set in other inverters or not can be checked.
REMARKS
When the copy destination inverter is not the FR-F700 series, "model error (
)" is displayed.
 flickers ... Why?
Set frequencies, etc. may be different. Check set frequencies.
FR-F720-02330 (FR-F740-01160) or less
FR-F720-03160 (FR-F740-01800) or more
Pr. 989 Setting
10
100
• Hold down        to verify.
2.
Screen at powering ON
     The monitor display appears.
Display
Operation
7.
Press         to read the parameter setting
     of the verified inverter to the operation panel.
1.
Move the operation panel to the  
     inverter to be verified.
     
• Move it during a stop.
Flicker ··· Parameter verification complete!!
4.
Turn        until              (parameter copy) 
     appears.
6.
Turn       to change it to the set value
     "   "(parameter copy verification mode).
8.
If there is no difference,              and   
     flicker to complete verification.
The frequency flickers
for about 30s
Flickering
 • If different parameters exist, different 
    parameter numbers and           flicker.
The parameter 
number read
 previously appears.
5.
Press         to read the present set
     value.
     "    "(initial value) appears.
3.
Press        to choose the parameter 
     setting mode.