Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
87
Limiting the output frequency
4
4.4 Limiting the output frequency
4.4.1
Maximum/minimum frequency (Pr. 1, Pr. 2, Pr. 18)
* The parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
(2) Set minimum frequency
⋅ Use Pr. 2 Minimum frequency to set the lower limit of the output frequency.
⋅ The output frequency is clamped by the Pr. 2 setting even the set frequency is lower than the Pr. 2 setting (The
frequency will not decrease to the Pr. 2 setting.) 
Purpose
Parameter that must be Set
Refer to Page
Set upper limit and lower limit of 
output frequency
Maximum/minimum 
frequency
Pr. 1, Pr. 2, Pr. 18
Perform operation by avoiding 
mechanical resonance points
Frequency jump
Pr. 31 to Pr. 36
You can limit the motor speed. Clamp the upper and lower limits of the output frequency.
Parameter 
Number
Name
Initial Value
200V class (400V class)
Setting Range
Description
1
Maximum frequency
02330 (01160) or less
120Hz
0 to 120Hz
Set the upper limit of the output 
frequency.
03160 (01800) or more
60Hz
2
Minimum frequency
0Hz
0 to 120Hz
Set the lower limit of the output 
frequency.
18
 
*
High speed maximum 
frequency
02330 (01160) or less
120Hz
120 to 400Hz
Set when performing the 
operation at 120Hz or more.
03160 (01800) or more
60Hz
(1) Set maximum frequency
⋅ Set the upper limit of the output frequency in Pr. 1 Maximum
frequency. If the value of the frequency command entered is
higher than the setting, the output frequency is clamped at the
maximum frequency.
⋅ When you want to perform operation above 120Hz, set the upper
limit of the output frequency to Pr. 18 High speed maximum
frequency
. (When Pr. 18 is set, Pr. 1 automatically switches to the
frequency of Pr. 18. When Pr. 18 is set, Pr. 18 automatically
switches to the frequency of Pr. 1.)
REMARKS
⋅ When performing operation above 60Hz using the frequency setting analog signal, change Pr. 125 (Pr. 126) (frequency setting
gain). If only Pr. 1 or Pr. 18 is changed, operation above 60Hz cannot be performed
REMARKS
⋅ When Pr. 15 Jog frequency is equal to or less than Pr. 2, the Pr. 15 setting has precedence over the Pr. 2 setting.
⋅ When stall prevention is activated to decrease the output frequency, the output frequency may drop to Pr. 2 or below.
 CAUTION
If the Pr. 2 setting is higher than the Pr. 13 Starting frequency value, note that the motor will run at the set 
frequency according to the acceleration time setting by merely switching the start signal ON, without entry of 
the command frequency.
♦ Parameters referred to 
Pr. 13 Starting frequency  
 Refer to page 104
Pr. 15 Jog frequency  
 Refer to page 95
Pr. 125 Terminal 2 frequency setting gain frequency, Pr. 126 Terminal 4 frequency setting gain frequency  
 Refer to page 177
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
Frequency setting
Clamped at the 
maximum frequency
Clamped at the
minimum frequency
5, 10V
(20mA)
0
(4mA)