Mitsubishi Electronics FR-F740P ユーザーズマニュアル

ページ / 410
195
4
4.17.6 Frequency setting signal (current) bias/gain adjustment method
(a)Method to adjust any point by application of voltage (current) across the terminals 2 and 5 (4 and 5).
Perform the following procedure to adjust the bias and gain of the frequency setting voltage (current) using the
operation panel FR-DU07.
Refer to page 193 for the details of parameters.
REMARKS
⋅ If the frequency meter (indicator) connected to across terminals FM and SD does not indicate exactly 60Hz, set calibration
parameter C0 FM terminal calibration(Refer to page 159)
⋅ If the gain and bias of frequency setting voltage (current) are too close, an error (
) may be displayed at setting.
5. 
Turn          to change it to the setting value 
of "    ".
4. 
Press        to read the present set value. 
"             " (initial value) appears.
3. 
Turn         until              appears.
Display
Analog voltage (current) 
value (%) across terminals 2 and 5 
(across terminals 4 and 5)
Flicker...Parameter setting complete!!
Flicker...Parameter setting complete!!
*
*
*The value is nearly 100 (%) in the maximum 
 position of the potentiometer.
*The value is nearly 100 (%) in the maximum 
 position of the potentiometer.
CAUTION
After performing the operation in step 10, do not touch         until 
completion of calibration.
(Adjustment completed)
Press        twice to show the next parameter (            ).
C0 to C7 setting 
is enabled.
Terminal 2 input Terminal 4 input
By turning        , you can read another parameter.
Press        to return to the              indication (step 8).
The parameter 
number read 
previously appears.
1. 
Confirm the RUN indicator and operation 
mode indicator 
    The inverter must be at a stop. 
    The inverter must be in the PU operation 
    mode. (Using       )
2. 
Press        to choose the parameter 
setting mode.
6. 
Press        to set.
7. 
8. 
Press        to display             .
9. 
Turn        until              (             ) appears.
Set to C4 Terminal 2 frequency setting  
gain.
10.
 Press        to display the analog voltage 
(current) value (%).
11. 
Apply a 5V (20mA) voltage (current). 
(Turn the external potentiometer 
connected across terminals 2 and 5 
(across terminals 4 and 5) to maximum 
(any position).)
12. 
Press        to set.
Operation
Terminal 4 input
Terminal 2 input