8.2
Motor starter
Motor starter version
DSte / RSte
sDSte / sRSte
Installation dimensions mm
(in parentheses: with protection guards)
Width
Height
Depth
294 (320)
215 (228)
159 (230)
Weight (g)
2880 g / 3130 g
3220 g / 3420 g
Control circuit (AS-i interface)
Slave type
Slave type
A/B slave
Suitable for AS-i master to spec.... (or higher)
AS-i Spec. 2.1 (M3)
AS-i slave profile IO.ID.ID2
7.A.E
ID1 code (factory setting)
7
Operating voltage U
AS-i
26.5 ... 31.6 V DC
Auxiliary voltage U
AUX
20.4 ... 28.8 V DC
Current consumption from AS-i (incl. 200 mA sensor supply)
< 300 mA
Current consumption from U
AUX
at 24 V (without digital output)
Max. 155 mA
Typ. 75 mA
Max. 15 mA / 175 mA
Typ. 10 mA / 75 mA
Main circuit
Max. power of three-phase motors at 400 V
Max. power of three-phase motors at 400 V
5.5 kW
4 kW
Max. rated operating current I
e
At 400 V
At 500 V
12 A
9 A
—
At 400 V
4 A
—
AC-1 / 2 / 3
AC-4
AC-53a (8 h operation)
At 400 V
—
9 A
Rated operating current
- Certification to EN 60947-1 Appendix N
- Certification to CSA and UL
400 V AC
600 V AC
400 V AC
480 V AC
Switching times
at 0.85 ... 1.1 x U
e
- Closing delay
- Opening delay
25 … 60 ms
15 … 40 ms
—
—
—
Mechanical service life of contactor
10 million
—
Electrical service life of contactor
See diagram
—
Permissible switching frequency
—
See diagram or
separate section