Technical specifications 
 
8.2 Motor starter 
 
M200D AS-Interface Basic 
90
 
Manual, 03/2009, A5E01668085-01 
 
 
 
Note 
This product is designed for environment A (industrial environments). In household 
environments, this device can cause unwanted radio interference. The user may be required 
to implement appropriate measures in this case. 
 
 
8.2 
Motor starter 
 
Motor starter version   
DSte / RSte 
sDSte / sRSte 
Installation dimensions mm  
(in parentheses: with protection guards) 
Width  
Height  
Depth 
294 (320) 
215 (228) 
159 (230) 
Weight (g)  
2880 g / 3130 g 
3220 g / 3420 g 
Control circuit (AS-i interface) 
Slave type 
A/B slave 
Suitable for AS-i master to spec.... (or higher) 
AS-i Spec. 2.1 (M3) 
AS-i slave profile IO.ID.ID2 
7.A.E 
ID1 code (factory setting) 
7  
Operating voltage U
AS-i
 
26.5 ... 31.6 V DC 
Auxiliary voltage U
AUX
  
20.4 ... 28.8 V DC 
Current consumption from AS-i (incl. 200 mA sensor supply) 
< 300 mA 
Current consumption from U
AUX 
at 24 V (without digital output) 
Max. 155 mA 
Typ. 75 mA 
Max. 15 mA / 175 mA 
Typ. 10 mA / 75 mA 
Main circuit 
Max. power of three-phase motors at 400 V 
5.5 kW 
4 kW 
Max. rated operating current I
e
  
At 400 V 
At 500 V 
12 A 
9 A 
— 
At 400 V 
4 A 
— 
AC-1 / 2 / 3 
 
AC-4 
AC-53a (8 h operation) 
At 400 V 
— 
9 A 
Rated operating current 
 - Certification to EN 60947-1 Appendix N 
 - Certification to CSA and UL 
 
400 V AC 
600 V AC 
 
400 V AC 
480 V AC 
Switching times  
at 0.85 ... 1.1 x U
e
 
- Closing delay  
- Opening delay 
25 … 60 ms 
15 … 40 ms 
— 
— 
Mechanical service life of contactor 
10 million 
— 
Electrical service life of contactor 
See diagram 
— 
Permissible switching frequency 
— 
See diagram or 
separate section