Trane Tracer ユーザーズマニュアル

ページ / 32
21
Configurable Parameters
Rover, Trane’s service tool, uses the 
unit type “heat pump” to determine 
and download unit configuration 
information, such as the default 
analog inputs, the default binary 
inputs, and the default binary output 
configurations. See Table 7 for 
default configurations for heat 
pumps.
Table 8: Heat pump heating or cooling operation.
Unit Type
Heat pump
Cooling Source
Compressor
Heating Source
Compressor (none for cooling only units)
Compressors
1 (2 for 2-compressor units)
Binary Outputs
BOP 1: Fan on (normally open)
BOP 2: Reversing valve (normally open)*
BOP 3: Not used
BOP 4: Compressor 1 (normally open)
BOP 5: Compressor 2 (normally open)**
BOP 6: Outdoor Air Damper (normally open)***
Binary Inputs
BI 1: Low temperature detection, circuit 2 (normally closed)* 
**
BI 2: Condensate overflow (normally closed)†
BI 3: Occupancy (normally open)
Analog Inputs
Zone: Space temperature (0.0 F calibration)
Set: Setpoint (0.0 F calibration)
Fan: Fan mode
AI 1: Leaving water temperature
AI 2: Discharge air temperature
Fan
Fan operation (heating): Cycling
Fan operation (cooling): Cycling
Fan speed default (heating): On/high
Fan speed default (cooling): On/high
Fan switch (hardwired): Enabled
Setpoints
Unoccupied cooling setpoint: 85 F
Occupied standby cooling: 78 F
Occupied cooling setpoint: 74 F
Occupied heating setpoint: 71 F
Occupied standby heating: 67 F
Unoccupied heating setpoint: 60 F
Cooling setpoint high limit: 115 F
Cooling setpoint low limit: 40 F
Heating setpoint high limit: 115 F
Heating setpoint low limit: 40 F
Thumbwheel set point: Enabled
Occupied Bypass 
Timer
120 minutes
Leaving Water 
Temperature
Low Limit
Unit specific (20 F ground source or 35 F standard)
Location Identifier
Unit specific (maximum of 30 characters)
Configuration
The heating and cooling setpoint 
high and low limits only apply to the 
occupied and occupied standby 
setpoints. These limits never apply 
to the unoccupied setpoints.
The leaving water temperature low 
limit is used for freeze protection of 
circuit 1 on heat pumps. Circuit 2 is 
protected by a binary low 
temperature detection device 
(freezestat) with a fixed trip point.
* BOP 2, BI1: Not used on cooling only units.
** BOP 5: Not used on signal compressor unit.
*** Configured but not required.
† Optional model number dependent
The occupied bypass time is used for timed 
override applications. The timed override 
timer is maintained in the unit controller. 
When the timed override is applicable, the 
controller reports “Occupied Bypass” as its 
effective occupancy mode.