Manual Output Testing the Heat 
Pump Configurations
The procedure for testing heat pump 
configurations is:
1.
Press and hold the Test button 
for at least three seconds to 
start the test mode.
2.
The test sequence resets 
diagnostics and turns off all 
outputs.
3.
Press the Test button several 
more times (no more than once 
per second) to advance through 
the test sequence.
Testing the Heat Pump
Configurations
The outputs are not subject to 
minimum times during the test 
sequence. However, the test 
sequence only permits one step per 
second which limits output time.
All outputs are exercised regardless 
what timer they are or are not 
configured for. For example, single 
compressor heat pumps function 
the same as two compressor units. 
For single compressor units, the 
cool 2 and heat 2 steps control the 
appropriate binary outputs, but do 
not affect unit operation.
Reversing valve and damper 
outputs cycle independent of 
configuration.
Pump Operation for
Systems with ZN510
Loop Controller
During Unoccupied, the pumps will 
be 
OFF
 but should be energized to 
test compressor operation. The user 
must override the pumps either at 
the ZN510 Loop Controller or by 
pushing the 
ON
 button of the zone 
sensor. This will send the units to an 
occupied bypass, which 
will turn the 
pumps on prior to operating 
manual output test. 
Table 12: Test sequence
Step
Fan
BOP 1
Reversing Valve
BOP 2
Compr 1
BOP 4
Compr 2
BOP 5
Damper
BOP 6
1. Off
Off
Off
Off 
Off
Closed
2. Fan on (At the beginning of step 2, the 
controller attempts to clear all diagnostics).
On
Off
Off
Off
Closed
3. Reversing Valve
On
On
Off
Off
Closed
4. Cool 1
On
On
On
Off
Closed
5.  Cool  2
On
On
On
On
Closed
6. Compressor(s) off
This stage helps avoid compressor cooling 
and heating in sequential steps by turning the 
compressors off prior to changing the 
reversing valve state.
On
Off
Off
Off
Closed
7. Heat 1
On
Off
On
Off
Closed
8. Heat 2
On
Off
On
On
Closed
9. Outdoor air damper
On
Off
Off
Off
Open
10. Exit
After the outdoor air damper step, the test 
sequence performs the exit step. This
initiates a reset and attempts to return the
controller to normal operation.
Troubleshooting