TROUBLESHOOTING
CER-TEMP 80 RECOVERY SYSTEM CHECKOUT PROCEDURE
Use this checkout for Cer-Temp 80 Recovery Systems. (For hot water supply application only)
Checkout Sequence
System Operation
Cause
Remedy
Contact
Incorrect
Set  tank  temperature 
control (thermostat) 20°F 
(10°C)  below  tank  water 
temperature.
Circulating pump and 
burner shut off.
With thermal balancer, 
pump off delay of 
approximately 2 minutes.
Pump and burner remain 
on.
Tank temperature control 
(thermostat) defective.
Replace.
System wiring is 
incorrect.
Correct wiring.
Circulating pump on.
Pump wired for 
continuous operation.
Correct wiring.
Burner on.
Gas valve stuck or 
defective.
Correct or replace 
valve.
System wiring is 
incorrect.
Correct wiring.
Set tank temperature 
control (thermostat) 20°F 
(10°C) above tank water 
temperature.
Circulating pump and 
burner on.
Circulating pump on.
High limit control set too 
low.
Replace. (If problem 
proven to be at this 
control by applying 
jumper to terminals.)
High limit control 
differential too wide.
System wiring is 
incorrect.
Correct wiring.
Coil protector switch has 
activated.
Remove control cover, 
depress reset button.
Gas valve or wiring 
defective.
Check wiring. Repair or 
replace valve.
Circulating pump and 
burner off.
Power off or system 
wiring is incorrect.
Check power supply 
and wiring.
Tank temperature control 
(thermostat) defective.
Replace.
Burner on.
System wiring is 
incorrect.
Correct wiring.
Boiler outlet temperature 
exceeds 210°F (100°C). Circulating pump on.
Circulating pump and 
burner on.
High limit control 
defective, or set too high 
(max. should be set at 
200°F).
Replace.
Set tank temperature 
control (thermostat) 
for desired water 
temperature.
System maintains desired 
water temperature.