Electric Eye Energy Sentinel System 
(Idle Pump Shut-off/Rinse Saver)
Circuit Explanation—
The electric eyes are infrared sensors located on the load end of the machine. The sensors
consist of an emitter and a receiver. These components switch the 120VAC control voltage
supplied to the pump timer.
When an object moving on the conveyor breaks the infrared beam between the eyes, contacts
(EER) close and complete the 120VAC circuit.
•  The pump timer resets and the pump motors start.
•  The pump timer and the final rinse timer begin to time down.
•  The pump timer resets each time the beam is broken.
Component Location—
The Emitter is mounted on the back of the load section. The Receiver is mounted on the front of
the load section.
Cleaning—
Be sure the emitter and receiver lenses are clean. Wipe the lenses clean with a soft cloth and
common rubbing alcohol.
Alignment—
Electric eyes do not normally require aligning except when replacing a defective unit.
The eyes are aligned visually. Make sure they oppose one another across the conveyor belt.
Replacement—
Remove the electric eye and disconnect the cable. Mount the new eye in its cover using the nut
provided. Recess the sensor 1/16" in the cover to protect the lens.
Infrared Electric Eyes
 
Receiver
Emitter
Green LED
Power ON
indicator
Yellow
output
indicator
_________________Basic Service
 
 Electrical Service
Basic Service • Electrical