Netgear GS716Tv2 - ProSAFE 16-Port Gigabit Managed Switch ハードウェアマニュアル

ページ / 35
18
GS716T/GS724T Gigabit Smart Switch 
Step 1: Prepare the Site
Before you install the switch, ensure the operating environment meets the operating 
environment requirements in the following table.
Table 3.  Site Requirements 
Characteristics Requirements
Mounting
Desktop installations - Provide a flat table or shelf surface.
Rack-mount installations - Use a 17-inch (48.3-centimeter) EIA standard 
equipment rack that is grounded and physically secure. The rack-mount kit supplied 
with the switch is also required.
Access
Locate the switch in a position that allows access to the front panel RJ-45 ports, view the 
front panel LEDs, and access power connector.
Power source
Provide a power source within 6 feet (1.8 meters) of the installation location. Power 
specifications for the switch are shown in 
. Ensure the AC outlet is not 
controlled by a wall switch, which can accidentally turn off power to the outlet and the 
switch.
Environmental
Temperature - Install the switch in a dry area, with ambient temperature between 0 
and 55ºC (32 and 131ºF). Keep the switch away from heat sources such as direct 
sunlight, warm air exhausts, hot-air vents, and heaters.
Operating humidity - The installation location should have a maximum relative 
humidity of 90%, non-condensing.
Ventilation - Do not restrict airflow by covering or obstructing air inlets on the sides 
of the switch. Keep at least 2 inches (5.08 centimeters) free on all sides for cooling. 
Be sure there is adequate airflow in the room or wiring closet where the switch is 
installed.
Operating conditions - Keep the switch at least 6 ft. (1.83 m) away from nearest 
source of electromagnetic noise, such as a photocopy machine.