Honeywell Bypass Drum Humidifier (HE120A) インストールガイド

ページ / 8
HE120, HE160 HUMIDIFIER INSTALLATION KIT
5
69-1571
Fig. 8. Adjusting HE160 water level.
INSTALLING BYPASS
1.
Use inside of  the 6 in. (155 mm) starter collar as a 
template to mark the opening for the bypass.
2.
Carefully cut the 6 in. (155 mm) opening for the 
starter collar. See Fig. 9. Use a drill, punch or awl 
to start the cut in the middle of the circle. Cut in an 
outward spiral to assist in controlling the cut.
Fig. 9. Cutting bypass opening.
3.
Assemble the summer shutoff damper into the 
starter collar. Verify that the damper rotates freely 
between the open and closed positions. Make sure 
handle will be accessible. Mark the damper closed 
position as summer and the open position as win-
ter. See Fig. 10.
Fig. 10. Installing starter collar.
4.
Remove liner to expose foam adhesive. Position 
starter collar over opening.
5.
Using sheet metal screws, connect starter collar to 
the duct and bypass duct from humidifier to starter 
collar. Be sure to secure the collar to the duct with 
sheet metal screws. See Fig. 11.
Fig. 11. Connecting bypass ducting.
IMPORTANT
To avoid sagging and stress on humidifier, add 
support if ducting is longer than 4 ft (1.25m). 
6.
Seal the duct connections with duct tape. 
7.
Reinstall the humidifier drum or disk assembly in 
the humidifier housing.
8.
Install the humidifier lid.
ENSURE TABS ON INLET AND 
MOTOR PLATE FIT INTO
SLOTS IN LID FLANGES
WATER
OVERFLOW HOLE
M20222
FLOAT ADJUSTMENT SLOT
STARTING 
HOLE
6 IN. ROUND TEMPLATE
M20172
SUMMER
WINTER
M20173
M20223